sensorProbeHumidityPercent
SPAGENT-MIB ·
.1.3.6.1.4.1.3854.1.2.2.1.17.1.3
Object
column
mandatory
Integer32
The relative humidity percentage measured by this sensor
Context
- MIB
- SPAGENT-MIB
- OID
.1.3.6.1.4.1.3854.1.2.2.1.17.1.3- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- sensorProbeHumidityEntry
- Table
- sensorProbeHumidityTable
- Siblings
- 59
Syntax
Integer32
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| sensorProbeHumidityDescription mandatory A Description of this sensor | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.3854.1.2.2.1.17.1.1 |
| sensorProbeHumidityLowCritical mandatory How low the relative humidity this sensor measures before it becomes critical | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.10 |
| sensorProbeHumidityRearm mandatory The percent relative humidity to rearm the status. For example if status goes from normal to warning, the humidity must go down spAnalogueRearm below warning before the status goe… | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.11 |
| sensorProbeHumidityRaw mandatory The unformatted, raw, A/D value in this sensor. Contains more resolution than the formated percentage. This number can go from 0 to 1023 depending on the input voltage | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.13 |
| sensorProbeHumidityLowVoltage mandatory SP Only: The low voltage range for use in AtoD conversion. | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.14 |
| sensorProbeHumidityHighVoltage mandatory SP Only: The high voltage range for use in AtoD conversion. | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.15 |
| sensorProbeHumidityEmailTrapLimit mandatory Enable email/trap limit feature | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.17 |
| sensorProbeHumidityEmailTrapSchedule mandatory SP Only: Email/trap limit schedule for this sensor | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.3854.1.2.2.1.17.1.18 |
| sensorProbeHumidityEmailTrapInterval mandatory Minimum time between each [email/trap:SP, only trap:CP8] (can be from 0 to 60 minutes) | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.19 |
| sensorProbeHumidityLocation mandatory The physical location of this sensor | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.3854.1.2.2.1.17.1.2 |
| sensorProbeHumiditySendNormalTrap mandatory Enable sending email/trap when sensor goes to normal | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.20 |
| sensorProbeHumidityDelayError mandatory Time in seconds after the sensor has been in error status before report as an error | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.21 |
| sensorProbeHumidityDelayNormal mandatory Time in seconds after the sensor change from error to normal before report as normal | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.22 |
| sensorProbeHumidityIndex mandatory The index into the Humidity sensor table | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.23 |
| sensorProbeHumidityAtoDAmountMaxVoltage mandatory The maximum scale of DC voltage conversion. | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.24 |
| sensorProbeHumidityAtoDAmountBaseVoltage mandatory The base scale of DC voltage conversion. | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.25 |
| sensorProbeHumidityAtoDTypeUnit mandatory Type of scale for use in DC voltage conversion. | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.26 |
| sensorProbeHumidityDcUnit mandatory Display unit in DC voltage conversion. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.3854.1.2.2.1.17.1.27 |
| sensorProbeHumidityAtoDJumper mandatory Selected voltage scale (jumper 0) in DC voltage conversion. | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.28 |
| sensorProbeHumidityRelayCycleTime mandatory Relay toggle period in seconds for Cycle action. | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.29 |
| sensorProbeHumidityRelayOnPort mandatory The sensor port that the relay will listen to. If this is set to 255, then the relay will not listen to any sensor ports | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.30 |
| sensorProbeHumidityRelayActiveStatus mandatory Sensor status that will activate the relay | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.31 |
| sensorProbeHumidityRelayAction mandatory What the relay will do when the listened to port status turns to the specified active status. | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.32 |
| sensorProbeHumidityEmailInterval mandatory CP8 Only: Minimum time between each emial (can be from 0 to 60 minutes) | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.33 |
| sensorProbeHumidity4to20mAUnit mandatory Display unit in DC voltage conversion. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.3854.1.2.2.1.17.1.34 |
| sensorProbeHumidityIndexCount mandatory Number of Humidity sensor online | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.35 |
| sensorProbeHumidityOffset mandatory Humidity Offset reading | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.36 |
| sensorProbeHumiditySirenCycleTime mandatory Siren toggle period in seconds for Cycle action. | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.37 |
| sensorProbeHumiditySirenOnPort mandatory The sensor port that the siren will listen to. If this is set to 255, then the siren will not listen to any sensor ports | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.38 |
| sensorProbeHumiditySirenActiveStatus mandatory Sensor status that will activate the siren | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.39 |
| sensorProbeHumidityStatus mandatory The current status of this Sensor | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.4 |
| sensorProbeHumiditySirenAction mandatory What the siren will do when the listened to port status turns to the specified active status. | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.40 |
| sensorProbeHumidityAcknowledgement mandatory Acknowledged sensor error and stop notification | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.41 |
| sensorProbeHumiditySirenDelayAlarm mandatory Siren delay in seconds before start Alarm. | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.42 |
| sensorProbeHumidityURL mandatory Sensor URL link. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.3854.1.2.2.1.17.1.43 |
| sensorProbeHumidityOpenURL mandatory Open URL in this browser or open in a new window. | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.44 |
| sensorProbeHumidityDatacollectType mandatory Type of datacollect to collect. | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.45 |
| sensorProbeHumidityContTimeHighCritical mandatory Continuous time for this sensor to be in High Critical before accepting new Status. | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.46 |
| sensorProbeHumidityContTimeHighWarning mandatory Continuous time for this sensor to be in High Warning before accepting new Status. | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.47 |
| sensorProbeHumidityContTimeNormal mandatory Continuous time for this sensor to be in Normal before accepting new Status. | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.48 |
| sensorProbeHumidityContTimeLowWarning mandatory Continuous time for this sensor to be in Low Warning before accepting new Status. | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.49 |
| sensorProbeHumidityOnline mandatory If this Sensor is currently online | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.5 |
| sensorProbeHumidityContTimeLowCritical mandatory Continuous time for this sensor to be in Low Critical before accepting new Status. | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.50 |
| sensorProbeHumidityContTimeSensorError mandatory Continuous time for this sensor to be in Sensor Error before accepting new Status. | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.51 |
| sensorProbeHumidityCalendar mandatory Enable or disable the calendar filtering working hours of sensor. | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.52 |
| sensorProbeHumiditySendNormalMail mandatory Enable sending email when sensor goes to normal | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.53 |
| sensorProbeHumiditySendTrap mandatory Enable sending trap when sensor change status | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.54 |
| sensorProbeHumiditySendMail mandatory Enable sending email when sensor change status | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.55 |
| sensorProbeIDCVVoltateRatio mandatory iDCV calibrate voltate ratio | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.56 |
| sensorProbeIDCVErrorFlag mandatory iDCV error flag | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.57 |
| sensorProbeIDCVCalibrate mandatory iDCV calibrate | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.58 |
| sensorProbeAirFlowProtocolType mandatory Air flow protocol type | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.59 |
| sensorProbeHumidityGoOnline mandatory To put online enter a 1, to take offline enter a 2 | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.6 |
| sensorProbeAirFlowSensitivity mandatory Air flow (AFS00) sensitivity | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.60 |
| sensorProbeAirFlowNormalState mandatory Air flow (AFS00) normal state | column | Enumeration | .1.3.6.1.4.1.3854.1.2.2.1.17.1.61 |
| sensorProbeAirFlowCalibrate mandatory Air flow (AFS00) normal state | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.62 |
| sensorProbeHumidityHighWarning mandatory How high the relative humidity this sensor measures before it sends a warning | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.7 |
| sensorProbeHumidityHighCritical mandatory How high the relative humidity this sensor measures before it becomes critical | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.8 |
| sensorProbeHumidityLowWarning mandatory How low the relative humidity this sensor measures before it sends a warning | column | Integer32 | .1.3.6.1.4.1.3854.1.2.2.1.17.1.9 |