adicomUpsBatteryStatus
SOCOMECUPS-ADICOM-MIB ·
.1.3.6.1.4.1.4555.1.1.5.1.2.1
Object
scalar
mandatory
Enumeration
The battery status of the unit
Context
- MIB
- SOCOMECUPS-ADICOM-MIB
- OID
.1.3.6.1.4.1.4555.1.1.5.1.2.1- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- adicomUpsBattery
- Siblings
- 5
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | unknown |
2 | batteryNormal |
3 | batteryLow |
4 | batteryDepleted |
5 | batteryDischarging |
6 | batteryFailure |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| adicomUpsSecondsOnBattery mandatory If the unit is on battery power, the elapsed time
since the unit last switched to battery power. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.5.1.2.2 |
| adicomUpsEstimatedMinutesRemaining mandatory An estimate of the time to battery charge depletion
under the present load conditions. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.5.1.2.3 |
| adicomUpsEstimatedChargeRemaining mandatory An estimate of the battery charge remaining expressed
as a percent of full charge. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.5.1.2.4 |
| adicomUpsBatteryVoltage mandatory The battery voltage in 0.1 Volt DC. | scalar | Integer32 | .1.3.6.1.4.1.4555.1.1.5.1.2.5 |