esPointValueInt

SL81-STD-MIB · .1.3.6.1.4.1.3052.5.1.1.1.1.6

Object

column mandatory r/w Integer32
A number referring to the value of a point on an
EventSensor.
              
If the point class is temperature, then this object
is the temperature in its configured scale (default
is Fahrenheit).
              
If the point class is contact closure or relay, then
this object is either 0 (open) or 1 (closed).
              
If the point class is humidity, then this object
is the percent relative humidity.
              
If the point class is analog input, then this
object is the signed input value in tenths of the
configured units.
              
For any point class except relay, this object is
read-only.
              
For relays, setting this object to 1 closes the
relay, while setting it to 0 opens it.  Setting it
to any value greater than 1 closes the relay for
that many seconds (up to 3600), after which time it
opens the relay.  This works regardless of the
control mode of the relay.

Context

MIB
SL81-STD-MIB
OID
.1.3.6.1.4.1.3052.5.1.1.1.1.6
Type
column
Access
readwrite
Status
mandatory
Parent
esPointEntry
Table
esPointTable
Siblings
8

Syntax

Integer32

Values & Constraints

Object Constraints
range: -32768-32767

Related Objects

Sibling Objects