fsGenInputPoint
SITEBOSS-530-STD-MIB ·
.1.3.6.1.4.1.3052.12.2.12.11.1.1.10
Object
column
r/w
Integer32
Which analog input point, on the specified eventsensor, that is associated with the fuel sensor.
Context
- MIB
- SITEBOSS-530-STD-MIB
- OID
.1.3.6.1.4.1.3052.12.2.12.11.1.1.10- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- fsGenEntry
- Table
- fuelSensorGeneralTable
- Siblings
- 17
Syntax
Integer32
Values & Constraints
Object Constraints
range: 519-1199
range: 0-62
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| fsGenIndex Which fuel sensor in the fuel sensor general config table. | column | Integer32 | .1.3.6.1.4.1.3052.12.2.12.11.1.1.1 |
| fsGenFilterAveraging Fuel sensor filter averaging factor. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.3052.12.2.12.11.1.1.11 |
| fsGenSysrepEnable Fuel sensor System Reporting enable. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.3052.12.2.12.11.1.1.12 |
| fsGenSysrepThreshold Fuel sensor System Reporting threshold (floating point value). | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.3052.12.2.12.11.1.1.13 |
| fsGenSysrepLimit Fuel sensor System Reporting limit. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.3052.12.2.12.11.1.1.14 |
| fsGenSysrepPackage Fuel sensor System Reporting package number. | column | Integer32 | .1.3.6.1.4.1.3052.12.2.12.11.1.1.15 |
| fsGenSysrepType Fuel sensor ASM profile type. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.3052.12.2.12.11.1.1.16 |
| fsGenEnable Fuel sensor enable. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.3052.12.2.12.11.1.1.17 |
| fsGenFuelType Type of fuel being measured: DIESEL, PROPANE,
NATURAL GAS, HYDROGEN, GASOLINE, OTHER. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.3052.12.2.12.11.1.1.18 |
| fsGenName Fuel sensor name. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.3052.12.2.12.11.1.1.2 |
| fsGenSensorType Type of fuel sensor in use; NONE disables the fuel sensor. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.3052.12.2.12.11.1.1.3 |
| fsGenDistanceUnit Distance units in use when setting and indicating tank dimensions. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.3052.12.2.12.11.1.1.4 |
| fsGenRawValueTop Analog input reading corresponding to the SENSOR FULL point. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.3052.12.2.12.11.1.1.5 |
| fsGenTopOffset Distance, in the specified distance unit, between the SENSOR FULL
point and the TANK FULL point. The value is positive if the
SENSOR FULL point is above the TANK FULL point, and … | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.3052.12.2.12.11.1.1.6 |
| fsGenRawValueBottom Analog input reading corresponding to the minimum fluid height
measurable by the fuel sensor. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.3052.12.2.12.11.1.1.7 |
| fsGenBottomOffset Distance, in the specified distance unit, between the SENSOR EMPTY
point and the TANK EMPTY point. The value is positive if the
SENSOR EMPTY point is above the TANK EMPTY point, … | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.3052.12.2.12.11.1.1.8 |
| fsGenInputES Which eventsensor contains the analog input associated with this fuel
sensor. Allowed values are 200 (for internal ES), or 1-16. | column | Integer32 | .1.3.6.1.4.1.3052.12.2.12.11.1.1.9 |