esPointValueStr
SITEBOSS-530-STD-MIB ·
.1.3.6.1.4.1.3052.12.1.1.1.1.7
Object
column
SNMPv2-TCDisplayString
A string referring to the value of a point on an
EventSensor.
For contact closures this object is either 'Open'
or 'Closed'.
For outputs this object is a concatenation of the
logical state and physical state, separated by '/'.
For a relay output this object can be one of the
following 4 possible values:
Active/Energized
Inactive/Energized
Active/De-energized
Inactve/De-energized
For a power output this object can be one of the
following 2 possible values:
On/Energized
Off/De-energized
For temperature and humidity point classes, this
object is the string representation of the
esPointValueInt object. For temperature, 'C' or
'F' is including in the string to indicate scale.
For analog inputs, this object is the string
representation of the plus/minus input in the
configured units appended with the unit name.
Context
- MIB
- SITEBOSS-530-STD-MIB
- OID
.1.3.6.1.4.1.3052.12.1.1.1.1.7- Type
- column
- Access
- readonly
- Status
- current
- Parent
- esPointEntry
Syntax
SNMPv2-TCDisplayString
Values & Constraints
Enumerated Values
0 | disable |
1 | enable |