esPointInEventState

SITEBOSS-530-STD-MIB · .1.3.6.1.4.1.3052.12.1.1.1.1.5

Object

column r/w SNMPv2-SMIInteger32
A number referring to the event state of a point
on an EventSensor.  This number can have different
meanings depending on the point class.
              
If the point class is temperature, humidity, or
analog input, then the values of this object are:
1=very low
2=low
3=normal
4=high
5=very high
              
For contact closures the values of this object are:
1=point in event state
2=point in normal state
              
For outputs the values of this object is the numeric
code for the logical state of the output: 1 or 2.  The
logical state of the output is either active/inactive for
relay outputs or on/off for power outputs.  The logical
state of the output has different nomenclature depending
on the type of the output (relay output or power output):
              
1=active (for relay output) or on (for power output)
2=inactive (for relay output) or off (for power output)
              
This is not necessarily representative of physical state
of the output.  Physical state is energized/de-energized,
for both relay and power outputs.  For relay outputs,
the active logical state corresponds to either the energized
physical state or the de-energized physical state depending
on how the relay output is configured.  For power outputs,
the on logical state always corresponds to the energized
physical state.
              
For any point class and any point, if the event
state is undefined, then the value of this object
is 0.
              
For any point class except output, this object is read-only.
For outputs, setting this object to 1 puts the output into
its active logical state.
              
Setting this object to 2 puts the output into its inactive
logical state.
              
Setting this object to any value greater than 2 puts the
output into its active logical state for that many seconds
(up to 3600), after which time it puts the output into its
inactive logical state.

Context

MIB
SITEBOSS-530-STD-MIB
OID
.1.3.6.1.4.1.3052.12.1.1.1.1.5
Type
column
Access
readwrite
Status
current
Parent
esPointEntry
Table
esPointTable
Siblings
10

Syntax

SNMPv2-SMIInteger32
Source
SNMPv2-SMIInteger32
Base type
Integer32

Values & Constraints

Object Constraints
range: 1-32
Type Constraints
range: -2147483648..2147483647

Related Objects

Sibling Objects