esPointInEventState

SITEBOSS-420-STD-MIB · .1.3.6.1.4.1.3052.42.1.1.1.1.5

Object

column r/w SNMPv2-SMIInteger32
A number referring to the event state of a point
on an EventSensor.  This number can have different
meanings depending on the point class.
              
If the point class is temperature, humidity, or
analog input, then the values of this object are:
1=very low
2=low
3=normal
4=high
5=very high
              
For contact closures the values of this object are:
1=point in event state
2=point in normal state
              
For relays the values of this object are:
1=relay energized (active)
2=relay de-energized (inactive)
              
For any point class and any point, if the event
state is undefined, then the value of this object
is 0.
              
For any point class except relay, this object is
read-only.  For relays, setting this object to 1
puts the relay into its active (energized) state.
Setting it to 2 puts the relay into its inactive
(de-energized) state.  Setting it to any
value greater than 2 puts the relay into its
active state for that many seconds (up to 3600),
after which time it puts the relay into its
inactive state.

Context

MIB
SITEBOSS-420-STD-MIB
OID
.1.3.6.1.4.1.3052.42.1.1.1.1.5
Type
column
Access
readwrite
Status
current
Parent
esPointEntry
Table
esPointTable
Siblings
6

Syntax

SNMPv2-SMIInteger32
Source
SNMPv2-SMIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647

Related Objects

Sibling Objects