Integer32
Index for table of power distribution objects, specifically the index that refers to which power distributor. A value of 200 means the internal power distributor. A value from 1 to 16 refers to an external power distributor (PowerBoss), and is the same value as esIndexES, which refers to the PowerBoss as an EventSensor in the eventSensorStatus object table. In other words, pdnIndexPD is the same as esIndexES: esIndexES is used to refer to the PowerBoss as an eventsensor (i.e., control outputs), while pdnIndexPD is used to refer to the PowerBoss when used for power distribution monitoring (i.e., to alarm on output current/voltage/fuse status).
Context
- MIB
- SITEBOSS-350-STD-MIB
- OID
.1.3.6.1.4.1.3052.18.1.5.4.1.1.1- Type
- column
- Access
- readonly
- Status
- current
- Parent
- pdnEntry
Syntax
Integer32
Values & Constraints
Object Constraints
range: 1-200