upduMeterType
RNX-UPDU-MIB ·
.1.3.6.1.4.1.55108.1.3.1.1.3
Object
column
Enumeration
Meter type: Tell if the meter is per-phase, per PDU, per module or for a single outlet or outlet group. For pduTotalCalc, phaseTotalCalc, moduleTotalCalc, the total is calculated (sum of the measurements of the underlying objects). For the other totals, it is measured.
Context
- MIB
- RNX-UPDU-MIB
- OID
.1.3.6.1.4.1.55108.1.3.1.1.3- Type
- column
- Access
- readonly
- Status
- current
- Parent
- upduMeterEntry
- Table
- upduMeterTable
- Siblings
- 13
Syntax
Enumeration
Values & Constraints
Enumerated Values
0 | pduTotal |
1 | pduTotalCalc |
2 | phaseTotal |
3 | phaseTotalCalc |
4 | moduleTotal |
5 | moduleTotalCalc |
6 | outlet |
7 | outletGroup |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upduMeterIndex Number of the meter on the Module. | column | Integer32 | .1.3.6.1.4.1.55108.1.3.1.1.1 |
| upduMeterUrms RMS voltage at a given instant. | column | mV MilliVolts | .1.3.6.1.4.1.55108.1.3.1.1.10 |
| upduMeterIrms RMS current at a given instant. | column | mA MilliAmperes | .1.3.6.1.4.1.55108.1.3.1.1.11 |
| upduMeterSystemName System-defined object name. | column | OctetString | .1.3.6.1.4.1.55108.1.3.1.1.12 |
| upduMeterCustomName User-configured unique object name. Write access has to be
explicitly enabled in the UPDU configuration (see SNMP
options). | column | OctetString | .1.3.6.1.4.1.55108.1.3.1.1.13 |
| upduMeterDescription User-configured description. Write access has to be
explicitly enabled in the UPDU configuration (see SNMP
options). | column | OctetString | .1.3.6.1.4.1.55108.1.3.1.1.14 |
| upduMeterName Meter name. | column | OctetString | .1.3.6.1.4.1.55108.1.3.1.1.2 |
| upduMeterEnergyP Positive active energy in watt hours. | column | Wh WattHours | .1.3.6.1.4.1.55108.1.3.1.1.4 |
| upduMeterEnergyR1 Reactive energy from quadrant R1 in volt-ampere reactives hours. | column | varh VoltAmpereReactiveHours | .1.3.6.1.4.1.55108.1.3.1.1.5 |
| upduMeterEnergyR4 Reactive energy from quadrant R4 in volt-ampere reactives hours. | column | varh VoltAmpereReactiveHours | .1.3.6.1.4.1.55108.1.3.1.1.6 |
| upduMeterPowerP Active power at a given instant. | column | W Watts | .1.3.6.1.4.1.55108.1.3.1.1.7 |
| upduMeterPowerQ Reactive power at a given instant. | column | var VoltAmpereReactives | .1.3.6.1.4.1.55108.1.3.1.1.8 |
| upduMeterPowerS Apparent power at a given instant. | column | VA VoltAmperes | .1.3.6.1.4.1.55108.1.3.1.1.9 |