upsBatteryStatus

RMS-MIB · .1.3.6.1.4.1.2769.10.22.13

Object

scalar mandatory Enumeration
The indication of the capacity remaining in the UPS
system's batteries.   A value of batteryNormal
indicates that the remaining run-time is greater than
upsConfigLowBattTime.  A value of batteryLow indicates
that the remaining battery run-time is less than or
equal to upsConfigLowBattTime.  A value of
batteryDepleted indicates that the UPS will be unable
to sustain the present load when and if the utility
power is lost (including the possibility that the
utility power is currently absent and the UPS is
unable to sustain the output).

Context

MIB
RMS-MIB
OID
.1.3.6.1.4.1.2769.10.22.13
Type
scalar
Access
readonly
Status
mandatory
Parent
ups
Siblings
20

Syntax

Enumeration

Values & Constraints

Enumerated Values
1unknown
2batteryNormal
3batteryLow
4batteryDepleted

Related Objects