rPDU2RCMSelfCheckCommand
PowerNet-PDU ·
.1.3.6.1.4.1.318.1.1.26.15.1.1.5
Object
column
mandatory
r/w
Enumeration
Getting this variable will return the RCM self checking status, 1: featureNotAvailable(-1) 2: success(1) 3: failed(2) 4: pending(3). Setting any of the selected pdu's rcm's variable to 1, will immediately start RCM Self Checking for all rcm of this pdu.
Context
- MIB
- PowerNet-PDU
- OID
.1.3.6.1.4.1.318.1.1.26.15.1.1.5- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- rPDU2RCMEntry
- Table
- rPDU2RCMTable
- Siblings
- 7
Syntax
Enumeration
Values & Constraints
Enumerated Values
-1 | featureNotAvailable |
1 | success |
2 | failed |
3 | pending |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDU2RCMIndex mandatory The index to the Rack PDU RCM table entry | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.15.1.1.1 |
| rPDU2RCMModule mandatory The user-defined Rack PDU numeric ID | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.15.1.1.2 |
| rPDU2RCMCurrent mandatory RCM RMS current. (mA) | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.15.1.1.3 |
| rPDU2RCMAlarmStatus mandatory RCM alarm status.
Setting the selected variable to 1,
will clear the over alarm. | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.15.1.1.4 |
| rPDU2RCMWarningThreshold mandatory Over Warning threshold of RCM current. (mA),
threshold can be set in the range of 15-300mA,
and must be lower or equal than Alarm threshold. | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.15.1.1.6 |
| rPDU2RCMAlarmThreshold mandatory Over Alarm threshold of RCM current. (mA),
threshold can be set in the range of 15~300 mA,
and must be higher or equal than Warning threshold. | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.15.1.1.7 |
| rPDU2RCMSelfCheckPeriod mandatory RCM Self-Checking Period. (day)
period can be set in the range of 1~365 days,
the rcm period on a single pdu is the same,
setting one of the selected pdu's rcm's period,
will chan… | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.15.1.1.8 |