rPDU2PhaseConfigModule
PowerNet-PDU ·
.1.3.6.1.4.1.318.1.1.26.6.1.1.2
Object
column
mandatory
Integer32
The user-defined Rack PDU numeric ID
Context
- MIB
- PowerNet-PDU
- OID
.1.3.6.1.4.1.318.1.1.26.6.1.1.2- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- rPDU2PhaseConfigEntry
- Table
- rPDU2PhaseConfigTable
- Siblings
- 7
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDU2PhaseConfigIndex mandatory The index to the Rack PDU phase configuration
table entry | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.6.1.1.1 |
| rPDU2PhaseConfigNumber mandatory The numeric phase ID | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.6.1.1.3 |
| rPDU2PhaseConfigOverloadRestriction mandatory This OID controls the behavior of a Switched Rack PDU
phase when an overload condition is possible and
additional outlets are requested to be turned on.
Setting thi… | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.6.1.1.4 |
| rPDU2PhaseConfigLowLoadCurrentThreshold mandatory User-defined low load phase current
threshold in Amps | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.6.1.1.5 |
| rPDU2PhaseConfigNearOverloadCurrentThreshold mandatory User-defined near phase overload warning
threshold in Amps | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.6.1.1.6 |
| rPDU2PhaseConfigOverloadCurrentThreshold mandatory User-defined phase overload current
threshold in Amps | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.6.1.1.7 |
| rPDU2PhaseConfigPhasePeakCurrentReset mandatory Setting this OID to reset (2) will cause the existing peak current value
to be replaced by the present load current value.
Getting this OID will do nothing and retu… | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.6.1.1.8 |