rPDU2DeviceStatusEnergy
PowerNet-PDU ·
.1.3.6.1.4.1.318.1.1.26.4.3.1.9
Object
column
mandatory
Integer32
A user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours. Models that do not support this feature will respond to this OID with a value of -1.
Context
- MIB
- PowerNet-PDU
- OID
.1.3.6.1.4.1.318.1.1.26.4.3.1.9- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- rPDU2DeviceStatusEntry
- Table
- rPDU2DeviceStatusTable
- Siblings
- 19
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDU2DeviceStatusIndex mandatory The index to the Rack PDU status table entry | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.3.1.1 |
| rPDU2DeviceStatusEnergyStartTime mandatory Indicates the date and time of the last device energy
meter reset. Models that do not support this feature will
respond to this OID with string 'notsupported'. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.10 |
| rPDU2DeviceStatusCommandPending mandatory Indicates whether or not the device
is processing a pending command. If
the commandPendingUnknown (3) value is
returned, all devices powered by the
Rack PDU should be shut down. … | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.3.1.11 |
| rPDU2DeviceStatusPowerSupplyAlarm mandatory Indicates a power supply alarm is active when value
equals alarm (2) | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.3.1.12 |
| rPDU2DeviceStatusPowerSupply1Status mandatory Indicates whether or not an alarm is active in Power
Supply 1 | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.3.1.13 |
| rPDU2DeviceStatusPowerSupply2Status mandatory Indicates whether or not an alarm is active in Power
Supply 2 | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.3.1.14 |
| rPDU2DeviceStatusOutletsEnergyStartTime mandatory Indicates the date and time of the last outlets energy
meter reset. Models that do not support this feature will
respond to this OID with string 'notsupported'. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.15 |
| rPDU2DeviceStatusApparentPower mandatory The apparent power consumption of the Rack PDU load in hundredths of kiloVoltAmps (kVA).
Models that do not support this feature will respond to this OID
with a value of -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.3.1.16 |
| rPDU2DeviceStatusPowerFactor mandatory The power factor of the Rack PDU load in hundredths. Models that do not support this feature
will respond to this OID with a value of -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.3.1.17 |
| rPDU2DeviceStatusNPSType mandatory The device NPS status:
notNPS (1) indicates the Rack PDU is not in an NPS group.
host (2) indicates the Rack PDU has been designated as a host in an NPS group.
Only one Rack PDU… | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.3.1.18 |
| rPDU2DeviceStatusResidualPower mandatory The measured device residual power from the PDU meters in hundredths of kiloVoltAmps. | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.3.1.19 |
| rPDU2DeviceStatusModule mandatory The user-defined Rack PDU numeric ID | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.3.1.2 |
| rPDU2DeviceStatusFrequency mandatory The measured device frequency from the PDU meters in tenths of Hz. | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.3.1.20 |
| rPDU2DeviceStatusName mandatory A user-defined string identifying the Rack PDU | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.3 |
| rPDU2DeviceStatusLoadState mandatory Indicates the present load status of the Rack PDU.
Models that do not support this feature will respond to this OID
with a value of notsupported (5). | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.3.1.4 |
| rPDU2DeviceStatusPower mandatory The power consumption of the Rack PDU load in hundredths of kilowatts.
Models that do not support this feature will respond to this OID
with a value of -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.3.1.5 |
| rPDU2DeviceStatusPeakPower mandatory The peak power consumption of the Rack PDU load in hundredths of kilowatts.
Models that do not support this feature will respond to this OID with a value
of -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.3.1.6 |
| rPDU2DeviceStatusPeakPowerTimestamp mandatory Indicates the date and time that peak power consumption occurred.
Models that do not support this feature will respond to this OID with string
'notsupported'. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.7 |
| rPDU2DeviceStatusPeakPowerStartTime mandatory Indicates the date and time of the last device peak power reset.
Models that do not support this feature will respond to this OID with string
'notsupported'. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.8 |