rPDU2DeviceConfigColdstartDelay
PowerNet-PDU ·
.1.3.6.1.4.1.318.1.1.26.4.1.1.6
Object
column
mandatory
r/w
Integer32
The amount of delay, measured in seconds, between when power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets. Allowed values are: -1 - never apply power automatically. 0 - apply power immediately. 1 to 300 - delay up to 300 seconds (5 minutes).
Context
- MIB
- PowerNet-PDU
- OID
.1.3.6.1.4.1.318.1.1.26.4.1.1.6- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- rPDU2DeviceConfigEntry
- Table
- rPDU2DeviceConfigTable
- Siblings
- 13
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDU2DeviceConfigIndex mandatory The index to the Rack PDU table entry | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.1.1.1 |
| rPDU2DeviceConfigDevicePeakPowerReset mandatory Setting this OID to reset (2) will cause the existing peak power value
to be replaced by the current load power value.
Getting this OID will do nothing and return t… | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.1.1.10 |
| rPDU2DeviceConfigDeviceEnergyReset mandatory Setting this OID to reset (2) will cause the device energy meter value
to be reset to zero.
Getting this OID in models that support this feature will do nothing
and… | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.1.1.11 |
| rPDU2DeviceConfigOutletsEnergyReset mandatory Setting this OID to reset (2) will cause the all outlet energy meter values
to be reset to zero.
Getting this OID will do nothing and return the noOperation(1) valu… | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.1.1.12 |
| rPDU2DeviceConfigOutletsPeakLoadReset mandatory Setting this OID to reset (2) will cause the all outlet peak load values
to be reset to zero.
Getting this OID will do nothing and return the noOperation(1) value.
… | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.1.1.13 |
| rPDU2DeviceConfigContact mandatory A user-defined string identifying the
person to contact regarding the Rack PDU | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.1.1.14 |
| rPDU2DeviceConfigModule mandatory The user-defined Rack PDU numeric ID | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.1.1.2 |
| rPDU2DeviceConfigName mandatory A user-defined string identifying the Rack PDU | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.1.1.3 |
| rPDU2DeviceConfigLocation mandatory A user-defined string identifying the location
of the Rack PDU | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.1.1.4 |
| rPDU2DeviceConfigDisplayOrientation mandatory Indicates the intended physical orientation
of the display.
displayNormal(1) indicates normal orientation
displayReverse(2) indicates upside down orientation | column | Enumeration | .1.3.6.1.4.1.318.1.1.26.4.1.1.5 |
| rPDU2DeviceConfigLowLoadPowerThreshold mandatory User-defined low power draw alarm threshold,
measured in tenths of kilowatts. Models that do
not support this feature will respond to this OID
with a value of -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.1.1.7 |
| rPDU2DeviceConfigNearOverloadPowerThreshold mandatory User-defined near power overload threshold,
measured in tenths of kilowatts. Models that do
not support this feature will respond to this OID
with a value of -1. | column | Integer32 | .1.3.6.1.4.1.318.1.1.26.4.1.1.8 |
| rPDU2DeviceConfigOverloadPowerThreshold mandatory User-defined power overload threshold,
measured in tenths of kilowatts. Models that do
not support this feature will respond to this OID