upsOutNumLines
NEXT-UPS-MIB ·
.0.1.1.5.6
Object
scalar
Integer32
The number of output lines utilized in this device. This variable indicates the number of rows in the output table.
Context
- MIB
- NEXT-UPS-MIB
- OID
.0.1.1.5.6- Type
- scalar
- Access
- readonly
- Status
- current
- Parent
- upsOutput
- Siblings
- 8
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsOutStatus For HVDC device.
char status[4];
status[0]status[1]:00, no output1; 01, line output1; 02, bat output1
status[2]status[3]:00, no output2; 01, line output2; 02, bat output2 | scalar | OctetString | .0.1.1.5.10 |
| upsOutFrequency The present output frequency. | column | 0.1Hertz UPS-MIBNonNegativeInteger | .0.1.1.5.7.1.9 |
| upsOutTtlApparentPower Total output apparent power . | scalar | 0.1VA UPS-MIBNonNegativeInteger | .0.1.1.5.3 |
| upsOutTtlTruePower Total output active(true) power . | scalar | 0.1Watts UPS-MIBNonNegativeInteger | .0.1.1.5.4 |
| upsOutTtlPercentLoad The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of
the percent load of true power capacity and the
percent load of VA. | scalar | percent Integer32 | .0.1.1.5.5 |
| upsOutTable A list of output table entries. The number of
entries is given by the value of upsOutputNumLines. | table | - | .0.1.1.5.7 |
| upsOutTtlVoltage Total output voltage . | scalar | 0.1vot Integer32 | .0.1.1.5.8 |
| upsOutTtlCurrent Total output current. | scalar | 0.1A Integer32 | .0.1.1.5.9 |