isDeviceConfigTemperatureHighCritical
ISPRO-MIB ·
.1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.6
Object
column
mandatory
r/w
Integer32
The threshold to trigger high critical alarm. the unit is 0.01 degree.
Context
- MIB
- ISPRO-MIB
- OID
.1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.6- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- isDeviceConfigTemperatureEntry
- Table
- isDeviceConfigTemperatureTable
- Siblings
- 12
Syntax
Integer32
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| isDeviceConfigTemperatureIndex mandatory The index to a temperature device entry. | column | Integer32 | .1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.1 |
| isDeviceConfigTemperatureLowCriticalState mandatory Enable/disable the set point to trigger low critical alarm. | column | IsproEnuEnable | .1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.10 |
| isDeviceConfigTemperatureHighWarningState mandatory Enable/disable the set point to trigger high warning alarm. | column | IsproEnuEnable | .1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.11 |
| isDeviceConfigTemperatureHighCriticalState mandatory Enable/disable the set point to trigger high critical alarm. | column | IsproEnuEnable | .1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.12 |
| isDeviceConfigTemperatureEventDO mandatory Set the trigger action of temperature events. If event asserted,
this will invert the digital output #1 or #2. | column | IsproEnuDO | .1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.13 |
| isDeviceConfigTemperatureName mandatory The temperature sensor name. | column | OctetString | .1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.2 |
| isDeviceConfigTemperatureLowWarning mandatory The set point to trigger low warning alarm. the unit is 0.01 degree. | column | Integer32 | .1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.3 |
| isDeviceConfigTemperatureLowCritical mandatory The threshold to trigger low critical alarm. the unit is 0.01 degree. | column | Integer32 | .1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.4 |
| isDeviceConfigTemperatureHighWarning mandatory The threshold to trigger high warning alarm. the unit is 0.01 degree. | column | Integer32 | .1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.5 |
| isDeviceConfigTemperatureHysteresis mandatory The set value to prevent too many alarms when temperature is hovering around the
set threshold. The unit is 0.01 | column | Integer32 | .1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.7 |
| isDeviceConfigTemperatureCalibration mandatory The set value to get the correct temperature according to your reference temperature. | column | IsproEnuTempCalibration | .1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.8 |
| isDeviceConfigTemperatureLowWarningState mandatory Enable/disable the set point to trigger low warning alarm. | column | IsproEnuEnable | .1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.9 |