hwAnaAlarmID
HUAWEI-ENVIRONMENT-MIB ·
.1.3.6.1.4.1.2011.6.1.1.2.1.12
Object
column
r/w
Enumeration
Analog alarm definition. Options: 1.temperature(1) -temperature alarm 2.humidity(2) -humidity alarm 3.voltage(3) -voltage alarm 4.electriccurrent(4) -electric current alarm 5.userDefinedAlarm0(100) -analog user-defined alarm 0 6.userDefinedAlarm1(101) -analog user-defined alarm 1 7.userDefinedAlarm2(102) -analog user-defined alarm 2 8.userDefinedAlarm3(103) -analog user-defined alarm 3 9.userDefinedAlarm4(104) -analog user-defined alarm 4 10.userDefinedAlarm5(105) -analog user-defined alarm 5 11.userDefinedAlarm6(106) -analog user-defined alarm 6 12.userDefinedAlarm7(107) -analog user-defined alarm 7 13.userDefinedAlarm8(108) -analog user-defined alarm 8 14.userDefinedAlarm9(109) -analog user-defined alarm 9 15.userDefinedAlarm10(110) -analog user-defined alarm 10 16.userDefinedAlarm11(111) -analog user-defined alarm 11 17.userDefinedAlarm12(112) -analog user-defined alarm 12 18.userDefinedAlarm13(113) -analog user-defined alarm 13 19.userDefinedAlarm14(114) -analog user-defined alarm 14 20.userDefinedAlarm15(115) -analog user-defined alarm 15 21.default(65535) -default analog alarm
Context
- MIB
- HUAWEI-ENVIRONMENT-MIB
- OID
.1.3.6.1.4.1.2011.6.1.1.2.1.12- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- hwAnaChannelEntry
- Table
- hwAnaChannelTable
- Siblings
- 14
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | temperature |
2 | humidity |
3 | voltage |
4 | electriccurrent |
100 | userDefinedAlarm0 |
101 | userDefinedAlarm1 |
102 | userDefinedAlarm2 |
103 | userDefinedAlarm3 |
104 | userDefinedAlarm4 |
105 | userDefinedAlarm5 |
106 | userDefinedAlarm6 |
107 | userDefinedAlarm7 |
108 | userDefinedAlarm8 |
109 | userDefinedAlarm9 |
110 | userDefinedAlarm10 |
111 | userDefinedAlarm11 |
112 | userDefinedAlarm12 |
113 | userDefinedAlarm13 |
114 | userDefinedAlarm14 |
115 | userDefinedAlarm15 |
65535 | default |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| hwAnaChannelIndex Index of the analog parameter that is monitored by the monitoring unit.
Range: 0 - 255 | column | Integer32 | .1.3.6.1.4.1.2011.6.1.1.2.1.1 |
| hwAnaAlarmState The status of the present monitored.
Options:
1.normal(1) -indicates that the measurement value is lower than the set high
limit of the alarm, and higher… | column | Enumeration | .1.3.6.1.4.1.2011.6.1.1.2.1.10 |
| hwAnaRowStatus RowStatus standard operation. The values 1 and 2 are supported currently.
1 indicates the activation status, and 2 indicates the non-activation status. | column | SNMPv2-TCRowStatus | .1.3.6.1.4.1.2011.6.1.1.2.1.11 |
| hwAnaMonitorState analog alarm(temperature,humidity,battery temperature) monitor flag value,
The value 1 enable monitor, value 2 disable monitor. | column | Enumeration | .1.3.6.1.4.1.2011.6.1.1.2.1.13 |
| hwAnaSignalHigh High limit of the analog signal.
invalid: 0x7fffffff. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.1.1.2.1.14 |
| hwAnaSignalLow Low limit of the analog signal.
invalid: 0x7fffffff. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.1.1.2.1.15 |
| hwAnaName Name of the analog parameter that is monitored by a monitoring unit. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.2011.6.1.1.2.1.2 |
| hwAnaType This object indicates the type of the sensor that is used to test the
Analog parameter.
Options:
1.invalid(-1) -there is no valid sensor
2.voltage(1) -voltage sensor currently
3… | column | Enumeration | .1.3.6.1.4.1.2011.6.1.1.2.1.3 |
| hwAnaMeasureType This object indicates the unit of the analog parameter that is tested. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.2011.6.1.1.2.1.4 |
| hwAnaWorkHigh High limit of the analog normal work | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.1.1.2.1.5 |
| hwAnaWorkLow Low limit of the analog normal work | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.1.1.2.1.6 |
| hwAnaAlmHigh High limit of the analog alarm. The alarm is produced
when the measurement value is higher than this value | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.1.1.2.1.7 |
| hwAnaAlmLow The low limit of the analog alarm. The alarm is produced
when the measurement value is lower than this value. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.1.1.2.1.8 |
| hwAnaCurrentValue The actual measurement value of the present analog.
Unit: milli
invalid: 0x7fffffff | column | milli SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.1.1.2.1.9 |