hm2DPIProfileIEC104AdvancedTypeIDList

HM2-FW-MIB · .1.3.6.1.4.1.248.11.79.1.3.21.3.1.11

Object

column r/w OctetString
The type IDs for this enforcer as string.
A type ID list has the syntax:
<val>
If more than one value is given for type ID list, values are
separated by a , sign (comma).
Note: The user can define any number between 0-255. The type ID must be a 
number (in decimal format).
All undefined type IDs are reserved for further compatible definitions.
Following type IDs are defined:
	0 Invalid type id invalid-0
	1 Single point information m-sp-na-1
	2 Single point information with time tag m-sp-ta-1
	3 Double point information m-dp-na-1
	4 Double point information with time tag m-dp-ta-1
	5 Step position information m-st-na-1
	6 Step position information with time tag m-st-ta-1
	7 Bit string of 32 bit m-bo-na-1
	8 Bit string of 32 bit with time tag m-bo-ta-1
	9 Measured value, normalized value m-me-na-1
	10 Measured value, normalized value with time tag m-me-ta-1
	11 Measured value, scaled value m-me-nb-1
	12 Measured value, scaled value with time tag m-me-tb-1
	13 Measured value, short floating point value m-me-nc-1
	14 Measured value, short floating point value with time tag m-me-tc-1
	15 Integrated totals m-it-na-1
	16 Integrated totals with time tag m-it-ta-1
	17 Event of protection equipment with time tag m-ep-ta-1
	18 Packed start events of protection equipment with time tag m-ep-tb-1
	19 Packed output circuit information of protection equipment with time tag m-ep-tc-1
	20 Packed single-point information with status change detection m-ps-na-1
	21 Measured value, normalized value without quality descriptor m-me-nd-1
	30 Single point information with time tag cp56time2a m-sp-tb-1
	31 Double point information with time tag cp56time2a m-dp-tb-1
	32 Step position information with time tag cp56time2a m-st-tb-1
	33 Bit string of 32 bit with time tag cp56time2a m-bo-tb-1
	34 Measured value, normalized value with time tag cp56time2a m-me-td-1
	35 Measured value, scaled value with time tag cp56time2a m-me-te-1
	36 Measured value, short floating point value with time tag cp56time2a m-me-tf-1
	37 Integrated totals with time tag cp56time2a m-it-tb-1
	38 Event of protection equipment with time tag cp56time2a m-ep-td-1
	39 Packed start events of protection equipment with time tag cp56time2a m-ep-te-1
	40 Packed output circuit information of protection equipment with time tag cp56time2a m-ep-tf-1
	45 Single command c-sc-na-1
	46 Double command c-dc-na-1
	47 Regulating step command c-rc-na-1
	48 Setpoint command, normalized value c-se-na-1
	49 Setpoint command, scaled value c-se-nb-1
	50 Setpoint command, short floating point value c-se-nc-1
	51 Bit string 32 bit c-bo-na-1
	58 Single command with time tag cp56time2a c-sc-ta-1
	59 Double command with time tag cp56time2a c-dc-ta-1
	60 Regulating step command with time tag cp56time2a c-rc-ta-1
	61 Setpoint command, normalized value with time tag cp56time2a c-se-ta-1
	62 Setpoint command, scaled value with time tag cp56time2a c-se-tb-1
	63 Setpoint command, short floating point value with time tag cp56time2a c-se-tc-1
	64 Bit string 32 bit with time tag cp56time2a c-bo-ta-1
	70 End of initialization m-ei-na-1
	100 (General-) Interrogation command c-ic-na-1
	101 Counter interrogation command c-ci-na-1
	102 Read command c-rd-na-1
	103 Clock synchronization command c-cs-na-1
	104 ( IEC 101 ) Test command c-ts-nb-1
	105 Reset process command c-rp-nc-1
	106 ( IEC 101 ) Delay acquisition command c-cd-na-1
	107 Test command with time tag cp56time2a c-ts-ta-1
	110 Parameter of measured value, normalized value p-me-na-1
	111 Parameter of measured value, scaled value p-me-nb-1
	112 Parameter of measured value, short floating point value p-me-nc-1
	113 Parameter activation p-ac-na-1
	120 File ready f-fr-na-1
	121 Section ready f-sr-na-1
	122 Call directory, select file, call file, call section f-sc-na-1
	123 Last section, last segment f-ls-na-1
	124 Ack file, Ack section f-af-na-1
	125 Segment f-sg-na-1
	126 f-dr-ta-1
	127 QueryLog - Request archive file f-sc-nb-1
	128-135 reserved for routing of messages
	136-255 reserved for special use

Context

MIB
HM2-FW-MIB
OID
.1.3.6.1.4.1.248.11.79.1.3.21.3.1.11
Type
column
Access
readwrite
Status
current
Parent
hm2DPIProfileIEC104Entry
Table
hm2DPIProfileIEC104Table
Siblings
15

Syntax

OctetString

Values & Constraints

Object Constraints
range: 0-1400

Related Objects

Sibling Objects