hm2DPIProfileDnp3FunctionCodeList

HM2-FW-MIB · .1.3.6.1.4.1.248.11.79.1.3.21.6.1.3

Object

column r/w OctetString
The function codes for this enforcer as string.
A function code has the syntax:
    <val>
If more than one value is given for a function code, values are
separated by a , sign (comma).
Note: The user can define any number between 0-255. The code must be a number (in decimal format).
Following function codes are defined by the DNP3 standard IEEE 1815-2012: 
	0	confirm 
	1	read 
	2	write 
	3	select 
	4	operate 
	5	direct_operate 
	6	direct_operate_nr 
	7	immed_freeze 
	8	immed_freeze_nr 
	9	freeze_clear 
	10	freeze_clear_nr 
	11	freeze_at_time 
	12	freeze_at_time_nr 
	13	cold_restart 
	14	warm_restart 
	15	initialize_data 
	16	initialize_appl 
	17	start_appl 
	18	stop_appl 
	19	save_config 
	20	enable_unsolicited 
	21	disable_unsolicited 
	22	assign_class 
	23	delay_measure 
	24	record_current_time 
	25	open_file 
	26	close_file 
	27	delete_file 
	28	get_file_info 
	29	authenticate_file 
	30	abort_file 
	31	activate_config 
	32	authenticate_req 
	33	authenticate_err 
	129	response 
	130	unsolicited_response 
	131	authenticate_resp

Context

MIB
HM2-FW-MIB
OID
.1.3.6.1.4.1.248.11.79.1.3.21.6.1.3
Type
column
Access
readwrite
Status
current
Parent
hm2DPIProfileDnp3Entry
Table
hm2DPIProfileDnp3Table
Siblings
8

Syntax

OctetString

Values & Constraints

Object Constraints
range: 1-1400

Related Objects

Sibling Objects