pdu2OutMonOutletVoltage
HAWK-I2-MIB ·
.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.5
Object
column
SNMPv2-SMIUnsigned32
The PDU outlet voltage. The value precision is tenths e.g. a value of 101 is 1.01 V.
Context
- MIB
- HAWK-I2-MIB
- OID
.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.5- Type
- column
- Access
- readonly
- Status
- current
- Parent
- pdu2OutletMonitorEntry
- Table
- pdu2OutletMonitorTable
- Siblings
- 13
Syntax
SNMPv2-SMIUnsigned32
- Source
- SNMPv2-SMIUnsigned32
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pdu2OutMonPduNumber The PDU index number. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.3711.24.2.1.1.1.7.1.1 |
| pdu2OutMonOutletkW The PDU outlet hkW. The value precision is hundredths e.g. a value of 101 is 1.01 kW. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.3711.24.2.1.1.1.7.1.10 |
| pdu2OutMonOutletPF The PDU outlet PF. The value precision is thousandths e.g. a value of 1001 is 1.001 PF. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.3711.24.2.1.1.1.7.1.11 |
| pdu2OutMonOutletkWh The PDU outlet kWh. The value precision is hundredths e.g. a value of 101 is 1.01 kWh. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.3711.24.2.1.1.1.7.1.12 |
| pdu2OutMonOutletBranchCircuitID The PDU outlet circuit ID. | column | DisplayString | .1.3.6.1.4.1.3711.24.2.1.1.1.7.1.13 |
| pdu2OutMonOutletPhaseID The PDU outlet phase ID. | column | DisplayString | .1.3.6.1.4.1.3711.24.2.1.1.1.7.1.14 |
| pdu2OutMonOutletNumber The PDU outlet number. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.3711.24.2.1.1.1.7.1.2 |
| pdu2OutMonRS The outlet monitor table row status. | column | SNMPv2-TCRowStatus | .1.3.6.1.4.1.3711.24.2.1.1.1.7.1.3 |
| pdu2OutMonOutletID The PDU outlet ID. | column | DisplayString | .1.3.6.1.4.1.3711.24.2.1.1.1.7.1.4 |
| pdu2OutMonOutletCurrent The PDU outlet current. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.3711.24.2.1.1.1.7.1.6 |
| pdu2OutMonOutletkVA The PDU outlet kVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.3711.24.2.1.1.1.7.1.7 |
| pdu2OutMonOutletPeakkVA The PDU outlet peak kVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.3711.24.2.1.1.1.7.1.8 |
| pdu2OutMonOutletPeakkVATimestamp The PDU outlet peak kVA timestamp. | column | UnsignedTimeTicks | .1.3.6.1.4.1.3711.24.2.1.1.1.7.1.9 |