pdu8341AbsEnergyActiveResettable
GUDEADS-PDU8341-MIB ·
.1.3.6.1.4.1.28507.65.1.5.1.2.1.13
Object
Resettable Absolute Active Energy counter. Writing '0' resets all resettable counter.
Context
- MIB
- GUDEADS-PDU8341-MIB
- OID
.1.3.6.1.4.1.28507.65.1.5.1.2.1.13- Type
- column
- Access
- readwrite
- Status
- current
- Units
- Wh
- Parent
- pdu8341PowerEntry
- Table
- pdu8341PowerTable
- Siblings
- 23
Syntax
Wh SNMPv2-SMIUnsigned32
- Source
- SNMPv2-SMIUnsigned32
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pdu8341PowerIndex Index of Power Channel entries | column | Integer32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.1 |
| pdu8341PowerApparent L Line Mean Apparent Power | column | VA SNMPv2-SMIInteger32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.10 |
| pdu8341PowerReactive L Line Mean Reactive Power | column | VAR SNMPv2-SMIInteger32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.11 |
| pdu8341AbsEnergyReactive Absolute Reactive Energy counter. | column | VARh SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.12 |
| pdu8341AbsEnergyReactiveResettable Resettable Absolute Reactive Energy counter. | column | VARh SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.14 |
| pdu8341ResetTime Time in seconds since last Energy
Counter reset. | column | s SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.15 |
| pdu8341ForwEnergyActive Forward Active Energy counter. | column | Wh SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.16 |
| pdu8341ForwEnergyReactive Forward Reactive Energy counter. | column | VARh SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.17 |
| pdu8341ForwEnergyActiveResettable Resettable Forward Active Energy counter. | column | Wh SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.18 |
| pdu8341ForwEnergyReactiveResettable Resettable Forward Reactive Energy counter. | column | VARh SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.19 |
| pdu8341ChanStatus 0 = data not active, 1 = data valid | column | Integer32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.2 |
| pdu8341RevEnergyActive Reverse Active Energy counter. | column | Wh SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.20 |
| pdu8341RevEnergyReactive Reverse Reactive Energy counter. | column | VARh SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.21 |
| pdu8341RevEnergyActiveResettable Resettable Reverse Active Energy counter. | column | Wh SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.22 |
| pdu8341RevEnergyReactiveResettable Resettable Reverse Reactive Energy counter. | column | VARh SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.23 |
| pdu8341ResidualCurrent Actual Residual Current on Power Channel.
According Typ A IEC 60755. Only visible on
models that support this feature. | column | mA SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.24 |
| pdu8341AbsEnergyActive Absolute Active Energy counter. | column | Wh SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.3 |
| pdu8341PowerActive Active Power | column | W SNMPv2-SMIInteger32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.4 |
| pdu8341Current Actual Current on Power Channel. | column | mA SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.5 |
| pdu8341Voltage Actual Voltage on Power Channel | column | V SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.6 |
| pdu8341Frequency Frequency of Power Channel | column | 0.01 hz SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.7 |
| pdu8341PowerFactor Power Factor of Channel between
-1.0 and 1.00 | column | 0.001 SNMPv2-SMIInteger32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.8 |
| pdu8341Pangle Phase Angle between Voltage
and L Line Current between
-180.0 and 180.0 | column | 0.1 degree SNMPv2-SMIInteger32 | .1.3.6.1.4.1.28507.65.1.5.1.2.1.9 |