upsStatusgen

GESINGLEUPS-MIB · .1.3.6.1.4.1.818.1.1.10.10.12

Object

scalar NonNegativeInteger32
The global UPS status is returned. Every bit reflects a specific 
status condition. Unused bits returns as 0. The status value can 
also be found on other commands. The value SNMPNOSUCHNAME means 
'invalid status' or 'status value non available'.
          
Status
        1  0000 0001h	upsStatusEcomodeIsOn
        2  0000 0002h	upsStatusBatteryIsCharging
        4  0000 0004h	upsStatusBatteryIsDischarging
        8  0000 0008h	upsStatusAlarmIsActive
       16  0000 0010h	upsStatusRectifierIsOn
       32  0000 0020h	upsStatusLowBattery
       64  0000 0040h	upsStatusOnBypass
      128  0000 0080h	upsStatusMainsBypassOK
      256  0000 0100h	upsStatusMainsRectifierOK
      512  0000 0200h	upsStatusDetourIsOn
     1024  0000 0400h	upsStatusAcousticAlarmIsOn
     2048  0000 0800h	upsStatusGlobalServiceCheck
     4096  0000 1000h	upsStatusInverterIsOn
     8192  0000 2000h	upsStatusNotInParallel (Q1 open)
    16384  0000 4000h	upsStatusResetLoadOff
    32768  0000 8000h	upsStatusLoadOff 
    65536  0001 0000h	upsStatusBoostMode 
   131072  0002 0000h	upsStatusBuckMode 
   262144  0004 0000h	upsStatusIemModeIsOn 
   524288  0008 0000h	upsStatus5thFilterIsOn 
  1048576  0010 0000h	upsStatus11thFilterIsOn
  2097152  0020 0000h	upsStatus2ndRectifierBridgeIsOn
  4194304  0040 0000h	- reserved -
  8388608  0080 0000h	- reserved -
 16777216  0100 0000h	- reserved -
 33554432  0200 0000h	- reserved -
 67108864  0400 0000h	- reserved -
134217728  0800 0000h	- reserved -
268435456  1000 0000h	upsGlobalParallelValues

Context

MIB
GESINGLEUPS-MIB
OID
.1.3.6.1.4.1.818.1.1.10.10.12
Type
scalar
Access
readonly
Status
current
Parent
upsGetSetgen
Siblings
23

Syntax

NonNegativeInteger32
Source
NonNegativeInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: 0..2147483647

Related Objects

Sibling Objects