powMonEntry
GEIST-MIB-V3 ·
.1.3.6.1.4.1.21239.2.3.1
Object
row
Entry in the power monitor table: each entry contains an index (powMonIndex) and other power monitoring details
Context
- MIB
- GEIST-MIB-V3
- OID
.1.3.6.1.4.1.21239.2.3.1- Type
- row
- Status
- current
- Parent
- powMonTable
- Table
- powMonTable
- Children
- 17
Syntax
No syntax metadata recorded.
Values & Constraints
Object Constraints
range: 0-48
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| powMonIndex Table entry index value | column | Integer32 | .1.3.6.1.4.1.21239.2.3.1.1 |
| powMonDeciAmps Current reading for DeciAmps | column | 0.1 Amps (rms) SNMPv2-SMIGauge32 | .1.3.6.1.4.1.21239.2.3.1.10 |
| powMonRealPower Current reading for Real Power | column | Watts SNMPv2-SMIGauge32 | .1.3.6.1.4.1.21239.2.3.1.11 |
| powMonApparentPower Current reading for Apparent Power | column | Volt-Amps SNMPv2-SMIGauge32 | .1.3.6.1.4.1.21239.2.3.1.12 |
| powMonPowerFactor Current reading for Power Factor | column | % Integer32 | .1.3.6.1.4.1.21239.2.3.1.13 |
| powMonOutlet1 Outlet 1 Trap | column | Outlet 1 Integer32 | .1.3.6.1.4.1.21239.2.3.1.14 |
| powMonOutlet2 Outlet 2 Trap | column | Outlet 2 Integer32 | .1.3.6.1.4.1.21239.2.3.1.15 |
| powMonOutlet1StatusTime Seconds Since Outlet 1 Last Changed Its Status | column | seconds SNMPv2-SMIGauge32 | .1.3.6.1.4.1.21239.2.3.1.16 |
| powMonOutlet2StatusTime Seconds Since Outlet 2 Last Changed Its Status | column | seconds SNMPv2-SMIGauge32 | .1.3.6.1.4.1.21239.2.3.1.17 |
| powMonSerial Serial Number | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.21239.2.3.1.2 |
| powMonName Friendly Name | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.21239.2.3.1.3 |
| powMonAvail Is device currently plugged in? | column | SNMPv2-SMIGauge32 | .1.3.6.1.4.1.21239.2.3.1.4 |
| powMonkWattHrs Current reading for kWatt-Hours | column | kWh SNMPv2-SMIGauge32 | .1.3.6.1.4.1.21239.2.3.1.5 |
| powMonVolts Current reading for Volts | column | Volts (rms) SNMPv2-SMIGauge32 | .1.3.6.1.4.1.21239.2.3.1.6 |
| powMonVoltMax Current reading for Volts (Max) | column | Volts (rms) SNMPv2-SMIGauge32 | .1.3.6.1.4.1.21239.2.3.1.7 |
| powMonVoltMin Current reading for Volts (Min) | column | Volts (rms) SNMPv2-SMIGauge32 | .1.3.6.1.4.1.21239.2.3.1.8 |
| powMonVoltPeak Current reading for Volts (Peak) | column | Volts (rms) SNMPv2-SMIGauge32 | .1.3.6.1.4.1.21239.2.3.1.9 |