podInputPhaseConfigOverloadRestriction
ENLOGIC-PDU2-MIB ·
.1.3.6.1.4.1.38446.3.3.2.1.3
Object
column
r/w
Enumeration
This OID controls the behavior of a Switched PDU Input Phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Input Phase to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Input Phase to turn on if the podInputPhaseConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Input Phase to turn on if the podInputPhaseConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
Context
- MIB
- ENLOGIC-PDU2-MIB
- OID
.1.3.6.1.4.1.38446.3.3.2.1.3- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- podInputPhaseConfigEntry
- Table
- podInputPhaseConfigTable
- Siblings
- 16
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | alwaysAllowTurnOn |
2 | restrictOnUpperWarning |
3 | restrictOnUpperCritical |
4 | notSupported |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| podInputPhaseConfigIndex The index of the PDU Input Phase configuration table entry | column | Integer32 | .1.3.6.1.4.1.38446.3.3.2.1.1 |
| podInputPhaseConfigVoltageUpperCriticalThreshold User-defined upper critical input phase voltage alarm threshold in Volts(V). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.3.3.2.1.10 |
| podInputPhaseConfigVoltageUpperWarningThreshold User-defined upper non-critical (warning) input phase voltage alarm threshold in Volts(V). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.3.3.2.1.11 |
| podInputPhaseConfigCurrentAlarmResetThreshold The hysteresis used for current alarm deassertions in hundredths of Amps(A). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.3.3.2.1.12 |
| podInputPhaseConfigCurrentAlarmStateChangeDelay The delay measured in samples before a current state is asserted. If the
value is zero, then the state is asserted as soon as it is
detected; if it is non-zero, say n, then the … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.38446.3.3.2.1.13 |
| podInputPhaseConfigCurrentEnabledThresholds A bit string indicating which current alarm thresholds are enabled. | column | Bits | .1.3.6.1.4.1.38446.3.3.2.1.14 |
| podInputPhaseConfigVoltageAlarmResetThreshold The hysteresis used for voltage alarm deassertions in Volts(V). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.3.3.2.1.15 |
| podInputPhaseConfigVoltageAlarmStateChangeDelay The delay measured in samples before a voltage state is asserted. If the
value is zero, then the state is asserted as soon as it is
detected; if it is non-zero, say n, then the … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.38446.3.3.2.1.16 |
| podInputPhaseConfigVoltageEnabledThresholds A bit string indicating which voltage alarm thresholds are enabled. | column | Bits | .1.3.6.1.4.1.38446.3.3.2.1.17 |
| podInputPhaseConfigCount The total number of Input Phases | column | Integer32 | .1.3.6.1.4.1.38446.3.3.2.1.2 |
| podInputPhaseConfigCurrentLowerCriticalThreshold User-defined lower critical input phase current alarm threshold in hundredths of Amps(A). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.3.3.2.1.4 |
| podInputPhaseConfigCurrentLowerWarningThreshold User-defined lower non-critical (warning) input phase current alarm threshold in hundredths of Amps(A). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.3.3.2.1.5 |
| podInputPhaseConfigCurrentUpperCriticalThreshold User-defined upper critical input phase current alarm threshold in hundredths of Amps(A). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.3.3.2.1.6 |
| podInputPhaseConfigCurrentUpperWarningThreshold User-defined upper non-critical (warning) input phase current alarm threshold in hundredths of Amps(A). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.3.3.2.1.7 |
| podInputPhaseConfigVoltageLowerCriticalThreshold User-defined lower critical input phase voltage alarm threshold in Volts(V). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.3.3.2.1.8 |
| podInputPhaseConfigVoltageLowerWarningThreshold User-defined lower non-critical (warning) input phase voltage alarm threshold in Volts(V). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.3.3.2.1.9 |