pduInputPhaseConfigOverloadRestriction
ENLOGIC-PDU2-MIB ·
.1.3.6.1.4.1.38446.1.3.2.1.3
Object
column
r/w
Enumeration
This OID controls the behavior of a Switched PDU Input Phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Input Phase to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
Context
- MIB
- ENLOGIC-PDU2-MIB
- OID
.1.3.6.1.4.1.38446.1.3.2.1.3- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- pduInputPhaseConfigEntry
- Table
- pduInputPhaseConfigTable
- Siblings
- 16
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | alwaysAllowTurnOn |
2 | restrictOnUpperWarning |
3 | restrictOnUpperCritical |
4 | notSupported |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pduInputPhaseConfigIndex The index of the PDU Input Phase configuration table entry | column | Integer32 | .1.3.6.1.4.1.38446.1.3.2.1.1 |
| pduInputPhaseConfigVoltageUpperCriticalThreshold User-defined upper critical input phase voltage alarm threshold in Volts(V). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.1.3.2.1.10 |
| pduInputPhaseConfigVoltageUpperWarningThreshold User-defined upper non-critical (warning) input phase voltage alarm threshold in Volts(V). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.1.3.2.1.11 |
| pduInputPhaseConfigCurrentAlarmResetThreshold The hysteresis used for current alarm deassertions in hundredths of Amps(A). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.1.3.2.1.12 |
| pduInputPhaseConfigCurrentAlarmStateChangeDelay The delay measured in samples before a current state is asserted. If the
value is zero, then the state is asserted as soon as it is
detected; if it is non-zero, say n, then the … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.38446.1.3.2.1.13 |
| pduInputPhaseConfigCurrentEnabledThresholds A bit string indicating which current alarm thresholds are enabled. | column | Bits | .1.3.6.1.4.1.38446.1.3.2.1.14 |
| pduInputPhaseConfigVoltageAlarmResetThreshold The hysteresis used for voltage alarm deassertions in Volts(V). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.1.3.2.1.15 |
| pduInputPhaseConfigVoltageAlarmStateChangeDelay The delay measured in samples before a voltage state is asserted. If the
value is zero, then the state is asserted as soon as it is
detected; if it is non-zero, say n, then the … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.38446.1.3.2.1.16 |
| pduInputPhaseConfigVoltageEnabledThresholds A bit string indicating which voltage alarm thresholds are enabled. | column | Bits | .1.3.6.1.4.1.38446.1.3.2.1.17 |
| pduInputPhaseConfigCount The total number of Input Phases | column | Integer32 | .1.3.6.1.4.1.38446.1.3.2.1.2 |
| pduInputPhaseConfigCurrentLowerCriticalThreshold User-defined lower critical input phase current alarm threshold in hundredths of Amps(A). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.1.3.2.1.4 |
| pduInputPhaseConfigCurrentLowerWarningThreshold User-defined lower non-critical (warning) input phase current alarm threshold in hundredths of Amps(A). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.1.3.2.1.5 |
| pduInputPhaseConfigCurrentUpperCriticalThreshold User-defined upper critical input phase current alarm threshold in hundredths of Amps(A). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.1.3.2.1.6 |
| pduInputPhaseConfigCurrentUpperWarningThreshold User-defined upper non-critical (warning) input phase current alarm threshold in hundredths of Amps(A). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.1.3.2.1.7 |
| pduInputPhaseConfigVoltageLowerCriticalThreshold User-defined lower critical input phase voltage alarm threshold in Volts(V). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.1.3.2.1.8 |
| pduInputPhaseConfigVoltageLowerWarningThreshold User-defined lower non-critical (warning) input phase voltage alarm threshold in Volts(V). | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.38446.1.3.2.1.9 |