rPDUPhaseCfgOverloadRestriction
DellrPDU-MIB ·
.1.3.6.1.4.1.674.10903.200.2.200.120.3.1.3
Object
column
mandatory
r/w
Enumeration
This OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigOverloadThreshold OID is exceeded.
Context
- MIB
- DellrPDU-MIB
- OID
.1.3.6.1.4.1.674.10903.200.2.200.120.3.1.3- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- rPDUPhaseConfigEntry
- Table
- rPDUPhaseConfigTable
- Siblings
- 5
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | alwaysAllowTurnON |
2 | restrictOnNearOverload |
3 | restrictOnOverload |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDUPhaseConfigIndex mandatory The index to the Rack PDU phase configuration table entry. | column | Integer32 | .1.3.6.1.4.1.674.10903.200.2.200.120.3.1.1 |
| rPDUPhaseConfigNumber mandatory The numeric phase ID. | column | Integer32 | .1.3.6.1.4.1.674.10903.200.2.200.120.3.1.2 |
| rPDUPhCfgLowLoadCurntThreshold mandatory The user-defined threshold for low phase current load, in Amps. | column | Integer32 | .1.3.6.1.4.1.674.10903.200.2.200.120.3.1.4 |
| rPDUPhCfgNerOverloadCurntThresh mandatory The user-defined near phase overload warning threshold in Amps. | column | Integer32 | .1.3.6.1.4.1.674.10903.200.2.200.120.3.1.5 |
| rPDUPhCfgOverloadCurntThreshold mandatory The user-defined phase overload current threshold in Amps. | column | Integer32 | .1.3.6.1.4.1.674.10903.200.2.200.120.3.1.6 |