rPDUDeviceConfigPeakPower
DellrPDU-MIB ·
.1.3.6.1.4.1.674.10903.200.2.200.110.3.1.9
Object
column
mandatory
Integer32
The highest input power level recorded by the connected devices in hundredths of kilowatt-hours.
Context
- MIB
- DellrPDU-MIB
- OID
.1.3.6.1.4.1.674.10903.200.2.200.110.3.1.9- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- rPDUDeviceConfigEntry
- Table
- rPDUDeviceConfigTable
- Siblings
- 12
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDUDeviceConfigIndex mandatory The index to the Rack PDU table entry. | column | Integer32 | .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.1 |
| rPDUDeviceCfgPeakPwrStartTime mandatory The time, in hh:mm:ss, when the device started recording the highest
input power level. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.10 |
| rPDUDeviceConfigPeakPwrCapTime mandatory The time, in hh:mm:ss, when the highest input power level was
recorded by the device. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.11 |
| rPDUDeviceCfgPeakPowerHeadroom mandatory The highest level of input power that is available to the connected
devices in hundredths of kilowatt-hours. | column | Integer32 | .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.12 |
| rPDUDeviceCfgEnergyStartTime mandatory The time, in hh:mm:ss, when the device started recording the input
energy level. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.13 |
| rPDUDeviceConfigName mandatory A user-defined string identifying the Rack PDU. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.2 |
| rPDUDeviceConfigLocation mandatory The Location of the Rack PDU. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.3 |
| rPDUDeviceConfigColdstartDelay mandatory The amount of delay, measured in seconds, between when power is
provided to the Rack PDU and when the Rack PDU provides basic
master power to the outlets. | column | Integer32 | .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.4 |
| rPDUDeviceCfgLowLoadPwrThresh mandatory The user-defined low power draw alarm threshold, measured in tenths
of kilowatts. | column | Integer32 | .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.5 |
| rPDUDeviceCfgNerOvloadPwrThresh mandatory The user-defined near power overload threshold, measured in tenths
of kilowatts. | column | Integer32 | .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.6 |
| rPDUDeviceCfgOverloadPwrThresh mandatory The user-defined power overload threshold, measured in tenths of
kilowatts. | column | Integer32 | .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.7 |
| rPDUDeviceConfigPowerHeadroom mandatory The amount of input power that is available to the connected
devices in hundredths of kilowatt-hours. | column | Integer32 | .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.8 |