upsSmartInputLineFailCause

DGPUPS-MIB · .1.3.6.1.4.1.17420.1.1.2.3.2.5

Object

scalar mandatory Enumeration
The reason for the occurrence of the last transfer
to UPS battery power.  The variable is set to
noTransfer(1) if there is no transfer yet.   The variable
is set to highLineVoltage(2) if the transfer to battery is
caused by an over voltage greater than the high transfer
voltage. The variable is set to brownout(3) if the duration
of the outage is greater than five seconds and the line
voltage is between 40 percent of the rated output voltage and
the low transfer voltage. The variable is set to blackout(4)
if the duration of the outage is greater than five seconds and
the line voltage is between 40 percent of the rated output voltage
and ground.  The variable is set to smallMomentarySag(5)
if the duration of the outage is less than five seconds and
the line voltage is between 40 percent of the rated output voltage
and the low transfer voltage.  The variable is set to
deepMomentarySag(6) if the duration of the outage is less
than five seconds and the line voltage is between 40 percent of the
rated output voltage and ground.

Context

MIB
DGPUPS-MIB
OID
.1.3.6.1.4.1.17420.1.1.2.3.2.5
Type
scalar
Access
readonly
Status
mandatory
Parent
upsSmartInput
Siblings
4

Syntax

Enumeration

Values & Constraints

Enumerated Values
1noTransfer
2highLineVoltage
3brownout
4blackout
5smallMomentarySag
6deepMomentarySag
7smallMomentarySpike
8largeMomentarySpike