upsSmartConfigUpsSleepTime
DGPUPS-MIB ·
.1.3.6.1.4.1.17420.1.1.2.5.2.11
Object
scalar
mandatory
r/w
Integer32
The time in minutes for the UPS to go to 'sleep' when
instructed. When in sleep mode, the UPS will not provide
output power regardless of the input line state. Once the
specified time has elapsed, output power will be restored.
This is a configuration setting. The UPS will not go to
sleep until told to do so by the manager from a management
station.
Any input value is allowed, however the UPS only recognizes
0 - 9999 minutes in one minute increments.
If the provided value is higher than the highest acceptable
value, the highest acceptable value is used.
Context
- MIB
- DGPUPS-MIB
- OID
.1.3.6.1.4.1.17420.1.1.2.5.2.11- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsSmartConfig
- Siblings
- 11
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsSmartConfigRatedOutputVoltage mandatory The nominal output voltage from the UPS in 1/10 VAC.
Possible values are 1000, 1200, 2080, 2200, 2250, 2300
and 2400.
NOTE: Only units that are 2200, 22… | scalar | Integer32 | .1.3.6.1.4.1.17420.1.1.2.5.2.1 |
| upsSmartConfigShutoffDelay mandatory The delay in seconds the UPS remains on after being told
to turn off. Allowed values are 12, 18, 24, 30, 36, 42,
48, 54, 60, 120, 180, 240, 300, 360, 420, 480, 540, and
600 secon… | scalar | Integer32 | .1.3.6.1.4.1.17420.1.1.2.5.2.10 |
| upsSmartConfigSetEEPROMDefaults mandatory WRITE: Resets the UPS EEPROM variables to default values.
READ: returns 0 | scalar | Enumeration | .1.3.6.1.4.1.17420.1.1.2.5.2.12 |
| upsSmartConfigHighTransferVolt mandatory The maximum line voltage in 1/10 VAC allowed before the
UPS system transfers to battery backup.
Allowed value depend on the UPS used:
120 Volt units all… | scalar | Integer32 | .1.3.6.1.4.1.17420.1.1.2.5.2.2 |
| upsSmartConfigLowTransferVolt mandatory The minimum line voltage in 1/10 VAC allowed before the
UPS system transfers to battery backup.
Allowable values depend on the UPS used:
120 Volt units … | scalar | Integer32 | .1.3.6.1.4.1.17420.1.1.2.5.2.3 |
| upsSmartConfigAlarm mandatory A flag indicating how the UPS should handle audible line fail
alarms. | scalar | Enumeration | .1.3.6.1.4.1.17420.1.1.2.5.2.4 |
| upsSmartConfigAlarmTimer mandatory The time in seconds after initial line failure at which the
UPS begins emitting audible alarms (beeping). This timer is
observerd only if the value of extControlAlarm is timed(2)… | scalar | Integer32 | .1.3.6.1.4.1.17420.1.1.2.5.2.5 |
| upsSmartConfigMinReturnCapacity mandatory The minimum battery capacity as a percent of full capacity
required before the UPS will return from a low battery
shutdown condition. In other words, the UPS will not
re-energize… | scalar | Integer32 | .1.3.6.1.4.1.17420.1.1.2.5.2.6 |
| upsSmartConfigSensitivity mandatory The sensitivity of the UPS to utility line abnormalities
or noises. | scalar | Enumeration | .1.3.6.1.4.1.17420.1.1.2.5.2.7 |
| upsSmartConfigLowBatteryRunTime mandatory The desired run time in seconds once the low battery
condition is reached. Allowed values are 120, 300, 420,
or 600 seconds. During this time the UPS will produce a
constant war… | scalar | Integer32 | .1.3.6.1.4.1.17420.1.1.2.5.2.8 |
| upsSmartConfigReturnDelay mandatory The delay in seconds after utility line power returns
before the UPS will turn on. This value is also used
when the UPS comes out of a reboot and before the UPS
wakes up from 'sl… | scalar | Integer32 | .1.3.6.1.4.1.17420.1.1.2.5.2.9 |