upsSmartConfigMinReturnCapacity

DGPUPS-MIB · .1.3.6.1.4.1.17420.1.1.2.5.2.6

Object

scalar mandatory r/w Integer32
The minimum battery capacity as a percent of full capacity
required before the UPS will return from a low battery
shutdown condition.  In other words, the UPS will not
re-energize the output until the battery capacity is equal
to this value. Allowed values are 0, 10, 25, or 90  percent.
                          
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value.  If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used.