outdoor2Tempr
DANTHERM-COOLING-MIB ·
.1.3.6.1.4.1.46651.1.1.5
Object
scalar
mandatory
celsius Integer32
Ambient Sensor 2 or Zone 2 Ambient Sensor. temperature in Degree Celcius
Context
- MIB
- DANTHERM-COOLING-MIB
- OID
.1.3.6.1.4.1.46651.1.1.5- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Units
- celsius
- Parent
- systemStatus
- Siblings
- 36
Syntax
celsius Integer32
Values & Constraints
Object Constraints
range: -41-101
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| onBoardTempr mandatory Controller On-Board temperature in Degree Celcius | scalar | celsius Integer32 | .1.3.6.1.4.1.46651.1.1.1 |
| fan1SpeedPercentage mandatory Fan 1 Speed in Percentage of Maximum Speed. Also represents Duty-Cycle of FAn Signal | scalar | percent Integer32 | .1.3.6.1.4.1.46651.1.1.10 |
| fan2SpeedPercentage mandatory Fan 2 Speed in Percentage of Maximum Speed. Also represents Duty-Cycle of FAn Signal | scalar | percent Integer32 | .1.3.6.1.4.1.46651.1.1.11 |
| damper1Position mandatory Damper 1 Shutter Open Percentage. 0% - Damper Closed. 100% - Damper completely open | scalar | percent Integer32 | .1.3.6.1.4.1.46651.1.1.12 |
| damper2Position mandatory Damper 2 Shutter Open Percentage. 0% - Damper Closed. 100% - Damper completely open | scalar | percent Integer32 | .1.3.6.1.4.1.46651.1.1.13 |
| humidity mandatory Internal or external humidity in Rh% | scalar | percent Integer32 | .1.3.6.1.4.1.46651.1.1.14 |
| dewpoint mandatory Internal or external DewPoint based on Humidity; in Degree Celcius | scalar | celsius Integer32 | .1.3.6.1.4.1.46651.1.1.15 |
| atmosphericPressure mandatory Atmospheric pressure or Pressure of installed enclosure in KiloPascal | scalar | KiloPascal Integer32 | .1.3.6.1.4.1.46651.1.1.16 |
| flowPressure mandatory Filter flow Pressure in Pascal | scalar | Pascal Integer32 | .1.3.6.1.4.1.46651.1.1.17 |
| roomTempr mandatory Room Sensor or Zone 1 Sensor temperature in Degree Celcius | scalar | celsius Integer32 | .1.3.6.1.4.1.46651.1.1.2 |
| heaterStatus mandatory heater operation status. 0 - Off; 1 - On | scalar | Enumeration | .1.3.6.1.4.1.46651.1.1.24 |
| shelter1Setpoint mandatory Shelter run time Cooling Set point in Single-Zone mode or Zone 1 Status in Dual-Zone mode respectively.
Cooling setpoint can be offset by following functions
RH function
Night mo… | scalar | celsius Integer32 | .1.3.6.1.4.1.46651.1.1.29 |
| hotSpotTempr mandatory Hot Spot Sensor or Zone 2 Sensor temperature in Degree Celcius | scalar | celsius Integer32 | .1.3.6.1.4.1.46651.1.1.3 |
| shelter2Setpoint mandatory Shelter run time Cooling Set point in Dual-Zone mode or Zone 2 Status.
Cooling setpoint can be offset by following functions
RH function
Night mode
Digital inputs | scalar | celsius Integer32 | .1.3.6.1.4.1.46651.1.1.30 |
| voltage mandatory System Voltage in DC. | scalar | VDC Integer32 | .1.3.6.1.4.1.46651.1.1.33 |
| fan1OpertdurHour mandatory Fan 1 operation duration - Hour | scalar | Hours Integer32 | .1.3.6.1.4.1.46651.1.1.36 |
| fan1OpertdurMin mandatory Fan 1 operation duration - Minute | scalar | Integer32 | .1.3.6.1.4.1.46651.1.1.37 |
| fan2OpertdurHour mandatory Fan 2 operation duration - Hour | scalar | Hours Integer32 | .1.3.6.1.4.1.46651.1.1.38 |
| fan2OpertdurMin mandatory Fan 2 operation duration - Minute | scalar | Integer32 | .1.3.6.1.4.1.46651.1.1.39 |
| outdoor1Tempr mandatory Ambient Sensor 1 or Zone 1 Ambient Sensor. temperature in Degree Celcius | scalar | celsius Integer32 | .1.3.6.1.4.1.46651.1.1.4 |
| aircon1OpertdurHour mandatory Airconditioner 1 operation duration - Hour | scalar | Hours Integer32 | .1.3.6.1.4.1.46651.1.1.40 |
| aircon1OpertdurMin mandatory Airconditioner 1 operation duration - Minute | scalar | Integer32 | .1.3.6.1.4.1.46651.1.1.41 |
| aircon2OpertdurHour mandatory Airconditioner 2 operation duration - Hour | scalar | Hours Integer32 | .1.3.6.1.4.1.46651.1.1.42 |
| aircon2OpertdurMin mandatory Airconditioner 2 operation duration - Minute | scalar | Integer32 | .1.3.6.1.4.1.46651.1.1.43 |
| heaterOpertdurHour mandatory Heater operation duration - Hour | scalar | Hours Integer32 | .1.3.6.1.4.1.46651.1.1.44 |
| heaterOpertdurMin mandatory Heater operation duration - Minute | scalar | Integer32 | .1.3.6.1.4.1.46651.1.1.45 |
| ccSN mandatory CC3000 Controller serial number | scalar | OctetString | .1.3.6.1.4.1.46651.1.1.46 |
| fanbox1SN mandatory Free cooling FanBox unit 1 serial number | scalar | OctetString | .1.3.6.1.4.1.46651.1.1.47 |
| fanbox2SN mandatory Free cooling FanBox unit 2 serial number | scalar | OctetString | .1.3.6.1.4.1.46651.1.1.48 |
| aircond1SN mandatory Aicodnitioner unit 1 serial number | scalar | OctetString | .1.3.6.1.4.1.46651.1.1.49 |
| aircond2SN mandatory Aicodnitioner unit 2 serial number | scalar | OctetString | .1.3.6.1.4.1.46651.1.1.50 |
| fwVersion mandatory CC3000 Firmware version | scalar | OctetString | .1.3.6.1.4.1.46651.1.1.51 |
| shelterTempr mandatory Shelter Temperature. Valid for Single-Zone solution | scalar | celsius Integer32 | .1.3.6.1.4.1.46651.1.1.6 |
| outdoorCombinedTempr mandatory Cobined minimum Outdoor Temeperature. Valid for Single-Zone solution | scalar | celsius Integer32 | .1.3.6.1.4.1.46651.1.1.7 |
| fan1RPM mandatory Fan 1 Rotation Per Minute | scalar | RPM Integer32 | .1.3.6.1.4.1.46651.1.1.8 |
| fan2RPM mandatory Fan 2 Rotation Per Minute | scalar | RPM Integer32 | .1.3.6.1.4.1.46651.1.1.9 |