cpqRackPowerSupplyInputLineStatus
CPQRACK-MIB ·
.1.3.6.1.4.1.232.22.2.5.1.1.1.15
Object
column
mandatory
Enumeration
The status of line input power.
Context
- MIB
- CPQRACK-MIB
- OID
.1.3.6.1.4.1.232.22.2.5.1.1.1.15- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- cpqRackPowerSupplyEntry
- Table
- cpqRackPowerSupplyTable
- Siblings
- 24
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | noError |
2 | lineOverVoltage |
3 | lineUnderVoltage |
4 | lineHit |
5 | brownOut |
6 | linePowerLoss |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| cpqRackPowerSupplyRack mandatory A number that uniquely specifies this rack. | column | Integer32 | .1.3.6.1.4.1.232.22.2.5.1.1.1.1 |
| cpqRackPowerSupplyCurPwrOutput mandatory The current power output of the power supply in watts.
The value will be -1 if the power supply does not report the
value. | column | Integer32 | .1.3.6.1.4.1.232.22.2.5.1.1.1.10 |
| cpqRackPowerSupplyPosition mandatory The position of the power supply within the power enclosure.
This will be -1 if the power enclosure does not report the
power supply information or it could not be … | column | Integer32 | .1.3.6.1.4.1.232.22.2.5.1.1.1.11 |
| cpqRackPowerSupplyIntakeTemp mandatory The current air temperature at the intake of the power supply
in degrees celsius.
The value will be -1 if the power supply does not report the
value. | column | Integer32 | .1.3.6.1.4.1.232.22.2.5.1.1.1.12 |
| cpqRackPowerSupplyExhaustTemp mandatory The current air temperature at the exhaust of the power supply
in degrees celsius.
The value will be -1 if the power supply does not report the
value. | column | Integer32 | .1.3.6.1.4.1.232.22.2.5.1.1.1.13 |
| cpqRackPowerSupplyStatus mandatory The status of the power supply. | column | Enumeration | .1.3.6.1.4.1.232.22.2.5.1.1.1.14 |
| cpqRackPowerSupplyPresent mandatory This specifies if the power supply described is present in the
enclosure. | column | Enumeration | .1.3.6.1.4.1.232.22.2.5.1.1.1.16 |
| cpqRackPowerSupplyCondition mandatory The condition of the power supply.
This value will be one of the following:
other(1)
The status could not be determined or not present.
… | column | Enumeration | .1.3.6.1.4.1.232.22.2.5.1.1.1.17 |
| cpqRackPowerSupplyEnclosureSerialNum mandatory The serial number of the power supply enclosure in which this
power supply resides.
The string will be empty if the enclosure does not report the
serial number or i… | column | OctetString | .1.3.6.1.4.1.232.22.2.5.1.1.1.18 |
| cpqRackPowerSupplyMeterPort mandatory The corresponding meter used to measure current for this power supply
The integer will be -1 if the enclosure does not report the value
or it could not be determine… | column | Integer32 | .1.3.6.1.4.1.232.22.2.5.1.1.1.19 |
| cpqRackPowerSupplyChassis mandatory A number that uniquely specifies this power enclosure in the rack. | column | Integer32 | .1.3.6.1.4.1.232.22.2.5.1.1.1.2 |
| cpqRackPowerSupplyInputCurrent mandatory Input current for the power supply
The integer will be -1 if the enclosure does not report the value
or it could not be determined. | column | Integer32 | .1.3.6.1.4.1.232.22.2.5.1.1.1.20 |
| cpqRackPowerSupplyInputPower mandatory Input wattage for the power supply
The integer will be -1 if the enclosure does not report the value
or it could not be determined. | column | Integer32 | .1.3.6.1.4.1.232.22.2.5.1.1.1.21 |
| cpqRackPowerSupplyInputVoltage mandatory Input voltage for the power supply
The integer will be -1 if the enclosure does not report the value
or it could not be determined. | column | Integer32 | .1.3.6.1.4.1.232.22.2.5.1.1.1.22 |
| cpqRackPowerSupplyOutputCurrent mandatory Output current for the power supply
The integer will be -1 if the enclosure does not report the value
or it could not be determined. | column | Integer32 | .1.3.6.1.4.1.232.22.2.5.1.1.1.23 |
| cpqRackPowerSupplyOutputPower mandatory Output wattage for the power supply
The integer will be -1 if the enclosure does not report the value
or it could not be determined. | column | Integer32 | .1.3.6.1.4.1.232.22.2.5.1.1.1.24 |
| cpqRackPowerSupplyOutputVoltage mandatory Output voltage for the power supply
The integer will be -1 if the enclosure does not report the value
or it could not be determined. | column | Integer32 | .1.3.6.1.4.1.232.22.2.5.1.1.1.25 |
| cpqRackPowerSupplyIndex mandatory A number that uniquely specifies this power supply in the enclosure. | column | Integer32 | .1.3.6.1.4.1.232.22.2.5.1.1.1.3 |
| cpqRackPowerSupplyEnclosureName mandatory The name of the power supply enclosure in which this power supply
resides.
The string will be empty if the enclosure does not report the
name or it could not be det… | column | OctetString | .1.3.6.1.4.1.232.22.2.5.1.1.1.4 |
| cpqRackPowerSupplySerialNum mandatory The serial number of the power supply.
The string will be empty if the power supply does not report the
serial number. | column | OctetString | .1.3.6.1.4.1.232.22.2.5.1.1.1.5 |
| cpqRackPowerSupplyPartNumber mandatory The part number of the power supply.
The string will be empty if the power supply does not report this
function. | column | OctetString | .1.3.6.1.4.1.232.22.2.5.1.1.1.6 |
| cpqRackPowerSupplySparePartNumber mandatory The spare part number of the power supply.
The string will be empty if the power supply does not report this
function. | column | OctetString | .1.3.6.1.4.1.232.22.2.5.1.1.1.7 |
| cpqRackPowerSupplyFWRev mandatory The firmware revision of the power supply.
The string will be empty if the power supply does not report the
firmware revision. | column | OctetString | .1.3.6.1.4.1.232.22.2.5.1.1.1.8 |
| cpqRackPowerSupplyMaxPwrOutput mandatory The maximum power output of the power supply in watts.
The value will be -1 if the power supply does not report the
value. | column | Integer32 | .1.3.6.1.4.1.232.22.2.5.1.1.1.9 |