pdu3GroupCurrentThStatus
CPQPOWER-MIB ·
.1.3.6.1.4.1.232.165.11.3.1.1.13
Object
column
mandatory
Enumeration
Status of the measured group current relative to the configured thresholds.
Context
- MIB
- CPQPOWER-MIB
- OID
.1.3.6.1.4.1.232.165.11.3.1.1.13- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- pdu3GroupEntry
- Table
- pdu3GroupTable
- Siblings
- 25
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | good |
2 | lowWarning |
3 | lowCritical |
4 | highWarning |
5 | highCritical |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pdu3GroupIndex mandatory Index for the Pdu3GroupEntry table. | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.1 |
| pdu3GroupVoltageThUpperCritical mandatory Upper critical threshold. Return value is divided by 10 to get one decimal point,
unit is in Volt. A negative value indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.10 |
| pdu3groupCurrentRating mandatory Rated current capacity of the group. Return value is divided by 100 to get two decimal points,
unit is in Amps. A negative value indicates that the hardware current capacity is… | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.11 |
| pdu3GroupCurrent mandatory A group current measurement value. Return value is divided by 100 to get two decimal points. | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.12 |
| pdu3GroupCurrentThLowerWarning mandatory Lower warning threshold. Return value is divided by 100 to get two decimal points. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.14 |
| pdu3GroupCurrentThLowerCritical mandatory Lower critical threshold. Return value is divided by 100 to get two decimal points. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.15 |
| pdu3GroupCurrentThUpperWarning mandatory Upper warning threshold. Return value is divided by 100 to get two decimal points. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.16 |
| pdu3GroupCurrentThUpperCritical mandatory Upper critical threshold. Return value is divided by 100 to get two decimal points. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.17 |
| pdu3GroupCurrentPercentLoad mandatory Current percent load, based on the rated current capacity. Units are
percentage, for example 80.9 % will be returned as 809. A negative
value indicates that this object is not a… | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.18 |
| pdu3GroupPowerVA mandatory A group VA value. Units are VA. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.19 |
| pdu3GroupName mandatory A descriptive name for the group. | column | OctetString | .1.3.6.1.4.1.232.165.11.3.1.1.2 |
| pdu3GroupPowerWatts mandatory A group power value. Units are Watts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.20 |
| pdu3GroupPowerWattHour mandatory An energy consumption value for each load segment. Units are kWh. This value can be reset to 0
using GUI. In that case, the pdu3GroupPowerWattHourTimer will be reset as well. … | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.21 |
| pdu3GroupPowerWattHourTimer mandatory Timestamp when group kilo Watt-hours (group kWh) is reset. | column | OctetString | .1.3.6.1.4.1.232.165.11.3.1.1.22 |
| pdu3GroupPowerFactor mandatory A group PF value. Return value is divided by 100, for example a power factor of 0.95 would be returned as 95.
A negative value indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.23 |
| pdu3GroupPowerVAR mandatory A measurement for group/load segment power reactive. Units are VAR. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.24 |
| pdu3GroupOutletCount mandatory The number of outlets in each group (breaker). | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.25 |
| pdu3GroupBreakerStatus mandatory Only applicable to groups with breaker. Indicates whether a breaker is turned
off or on. | column | Enumeration | .1.3.6.1.4.1.232.165.11.3.1.1.26 |
| pdu3GroupType mandatory The type of the group. (5) has no breaker | column | Enumeration | .1.3.6.1.4.1.232.165.11.3.1.1.3 |
| pdu3GroupVoltageMeasType mandatory Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
phas… | column | Enumeration | .1.3.6.1.4.1.232.165.11.3.1.1.4 |
| pdu3GroupVoltage mandatory Return value is divided by 10 to get one decimal point, unit is in Volt. | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.5 |
| pdu3GroupVoltageThStatus mandatory Status of the measured group voltage relative to the configured thresholds. | column | Enumeration | .1.3.6.1.4.1.232.165.11.3.1.1.6 |
| pdu3GroupVoltageThLowerWarning mandatory Lower warning threshold. Return value is divided by 10 to get one decimal point,
unit is in Volt. A negative value indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.7 |
| pdu3GroupVoltageThLowerCritical mandatory Lower critical threshold. Return value is divided by 10 to get one decimal point,
unit is in Volt. A negative value indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.8 |
| pdu3GroupVoltageThUpperWarning mandatory Upper warning threshold. Return value is divided by 10 to get one decimal point,
unit is in Volt. A negative value indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.3.1.1.9 |