pdu2OutletCurrentThStatus
CPQPOWER-MIB ·
.1.3.6.1.4.1.232.165.7.5.1.1.6
Object
column
mandatory
Enumeration
Status of the measured outlet current relative to the configured thresholds.
Context
- MIB
- CPQPOWER-MIB
- OID
.1.3.6.1.4.1.232.165.7.5.1.1.6- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- pdu2OutletEntry
- Table
- pdu2OutletTable
- Siblings
- 17
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | good |
2 | lowWarning |
3 | lowCritical |
4 | highWarning |
5 | highCritical |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pdu2OutletIndex mandatory Index for each outlet, value from 1 to the number of outlets per PDU. | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.1.1.1 |
| pdu2OutletCurrentThUpperCritical mandatory Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.1.1.10 |
| pdu2OutletCurrentCrestFactor mandatory Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.1.1.11 |
| pdu2OutletCurrentPercentLoad mandatory Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative
value indicates that this object is not avail… | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.1.1.12 |
| pdu2OutletVA mandatory A outlet VA value. Units are VA. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.1.1.13 |
| pdu2OutletWatts mandatory A outlet Watts value. Units are Watts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.1.1.14 |
| pdu2OutletWh mandatory A Watt-Hour value for each outlet. Units are WH.
This object is writable so that it can be reset to 0. When it is
written to, the pdu2OutletWhTimer will be reset updated as well… | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.1.1.15 |
| pdu2OutletWhTimer mandatory Timestamp (date and time) of outlet Watt-hours was last reset. | column | OctetString | .1.3.6.1.4.1.232.165.7.5.1.1.16 |
| pdu2OutletPowerFactor mandatory An outlet PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned
as 920. A negative value indicat… | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.1.1.17 |
| pdu2OutletVAR mandatory An outlet VAR value. Units are VAR. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.1.1.18 |
| pdu2OutletName mandatory A descriptive name for the outlet. | column | OctetString | .1.3.6.1.4.1.232.165.7.5.1.1.2 |
| pdu2OutletType mandatory Type of this outlet - C13, C19. | column | Enumeration | .1.3.6.1.4.1.232.165.7.5.1.1.3 |
| pdu2OutletCurrentRating mandatory Rated current capacity of this outlet. Units are milliamps. A negative
value indicates that the hardware current capacity is unknown. | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.1.1.4 |
| pdu2OutletCurrent mandatory A outlet current measurement value. Units are milliamps. | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.1.1.5 |
| pdu2OutletCurrentThLowerWarning mandatory Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.1.1.7 |
| pdu2OutletCurrentThLowerCritical mandatory Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.1.1.8 |
| pdu2OutletCurrentThUpperWarning mandatory Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.1.1.9 |