pdu2OutletControlPowerOnState
CPQPOWER-MIB ·
.1.3.6.1.4.1.232.165.7.5.2.1.5
Object
column
mandatory
r/w
Enumeration
Determines the outlet state when power is applied to the unit. 1 : not restart at device startup 2 : should sequence back ON in line with outletControlSequenceTime 3 : should take the state the outlet had when power was lost. If the state was ON, should sequence back ON in line with outletControlSequenceTime.
Context
- MIB
- CPQPOWER-MIB
- OID
.1.3.6.1.4.1.232.165.7.5.2.1.5- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- pdu2OutletControlEntry
- Table
- pdu2OutletControlTable
- Siblings
- 8
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | off |
2 | on |
3 | lastState |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pdu2OutletControlStatus mandatory current state of a control outlet. | column | Enumeration | .1.3.6.1.4.1.232.165.7.5.2.1.1 |
| pdu2OutletControlOffCmd mandatory When write, once issued, the outlet will turn Off immediately.
0-n: Time in seconds until the outlet command is issued
-1: Cancel a pending outlet Off command
When read, returns … | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.2.1.2 |
| pdu2OutletControlOnCmd mandatory When write, once issued, the outlet will turn On immediately.
0-n: Time in seconds until the outlet command is issued
-1: Cancel a pending outlet On command
When read, returns -1… | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.2.1.3 |
| pdu2OutletControlRebootCmd mandatory When write, for outlets that are On prior to this Reboot command, they will
switch Off immediately when the command is issued, remain Off for
outletControlRebootOffTime seconds,… | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.2.1.4 |
| pdu2OutletControlSequenceDelay mandatory Time delay in seconds from when a Global Sequence On command is issued to
when the command is executed on this outlet. This delay is also used as a power-on
delay. Set to -1 to e… | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.2.1.6 |
| pdu2OutletControlRebootOffTime mandatory Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command. | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.2.1.7 |
| pdu2OutletControlSwitchable mandatory Determines the outlet capability to be controlled On/Off from the communication channels.
1 : control On/Off enabled
2 : control On/Off disabled. | column | Enumeration | .1.3.6.1.4.1.232.165.7.5.2.1.8 |
| pdu2OutletControlShutoffDelay mandatory Time delay in seconds that could be taken in account before shutting of the outlet.
An application which need to shutoff properly an outlet will read this parameter first
then wri… | column | Integer32 | .1.3.6.1.4.1.232.165.7.5.2.1.9 |