pdu2InputEntry
CPQPOWER-MIB ·
.1.3.6.1.4.1.232.165.7.2.1.1
Object
row
mandatory
The ident table entry containing the VA, Watts, WH, etc.
Context
- MIB
- CPQPOWER-MIB
- OID
.1.3.6.1.4.1.232.165.7.2.1.1- Type
- row
- Status
- mandatory
- Parent
- pdu2InputTable
- Table
- pdu2InputTable
- Children
- 9
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pdu2InputType mandatory Type of input - single phase, split phase, three phase delta, or three
phase wye. | column | Enumeration | .1.3.6.1.4.1.232.165.7.2.1.1.1 |
| pdu2InputFrequency mandatory The measured input frequency from the PDU meters in tenths of Hz. | column | Integer32 | .1.3.6.1.4.1.232.165.7.2.1.1.2 |
| pdu2InputFrequencyStatus mandatory Status of the measured input frequency relative to the nominal frequency and the admitted tolerance. | column | Enumeration | .1.3.6.1.4.1.232.165.7.2.1.1.3 |
| pdu2InputPowerVA mandatory A total input VA of all phases. Units are VA. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.7.2.1.1.4 |
| pdu2InputPowerWatts mandatory A total input Watts of all phases. Units are Watts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.7.2.1.1.5 |
| pdu2InputPowerWattHour mandatory A total input Watt-Hour value for all phases. Units are WH. This value can be reset to 0
using GUI. In that case, the pdu2InputPowerWattHourTimer will be reset as well
A negat… | column | Integer32 | .1.3.6.1.4.1.232.165.7.2.1.1.6 |
| pdu2InputPowerWattHourTimer mandatory A Timestamp of when the Total Input WH was last reset. | column | OctetString | .1.3.6.1.4.1.232.165.7.2.1.1.7 |
| pdu2InputPowerFactor mandatory An input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920.
A negative value indicates that th… | column | Integer32 | .1.3.6.1.4.1.232.165.7.2.1.1.8 |
| pdu2InputPowerVAR mandatory An input VAR value. Units are VAR. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.7.2.1.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| pdu2IdentIndex mandatory Index for the Pdu2IdentEntry table. | column | Integer32 | .1.3.6.1.4.1.232.165.7.1.2.1.1 |