pdu2HumidityThLowerCritical
CPQPOWER-MIB ·
.1.3.6.1.4.1.232.165.7.4.3.1.7
Object
column
mandatory
Integer32
Lower critical threshold. Units are 0.1 %RH. A negative value indicates that this object is not available.
Context
- MIB
- CPQPOWER-MIB
- OID
.1.3.6.1.4.1.232.165.7.4.3.1.7- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- pdu2HumidityEntry
- Table
- pdu2HumidityTable
- Siblings
- 8
Syntax
Integer32
Values & Constraints
Object Constraints
range: -1-1000
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pdu2HumidityIndex mandatory A unique value for each humidity probe measurement. Its value
ranges from 1 to pdu2HumidityCount per pdu. | column | Integer32 | .1.3.6.1.4.1.232.165.7.4.3.1.1 |
| pdu2HumidityName mandatory A descriptive name for the humidity probe. | column | OctetString | .1.3.6.1.4.1.232.165.7.4.3.1.2 |
| pdu2HumidityProbeStatus mandatory Indicates whether a probe is connected or not. | column | Enumeration | .1.3.6.1.4.1.232.165.7.4.3.1.3 |
| pdu2HumidityValue mandatory Units are tenths of a percent relative humidity. Divide the value by 10 to get %RH. | column | Integer32 | .1.3.6.1.4.1.232.165.7.4.3.1.4 |
| pdu2HumidityThStatus mandatory Status of the measured humidity relative to the configured thresholds. | column | Enumeration | .1.3.6.1.4.1.232.165.7.4.3.1.5 |
| pdu2HumidityThLowerWarning mandatory Lower warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.7.4.3.1.6 |
| pdu2HumidityThUpperWarning mandatory Upper warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.7.4.3.1.8 |
| pdu2HumidityThUpperCritical mandatory Upper critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.7.4.3.1.9 |