mpduOutputStatus
CPQPOWER-MIB ·
.1.3.6.1.4.1.232.165.5.2.1.1.2
Object
The overall status of the device: off, on, problem. StringLength=[7].
Context
- MIB
- CPQPOWER-MIB
- OID
.1.3.6.1.4.1.232.165.5.2.1.1.2- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- mpduOutputEntry
- Table
- mpduOutputTable
- Siblings
- 12
Syntax
RFC1213-MIBDisplayString
- Source
- RFC1213-MIBDisplayString
- Base type
OctetString
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| mpduOutputIndex mandatory Index for the MpduOutputEntry table. | column | Integer32 | .1.3.6.1.4.1.232.165.5.2.1.1.1 |
| mpduOutputPowerFactor mandatory The power factor is presented in 1/100 of the unit i.e.
98 is 0.98. A value of -1 will be returned if the power factor is unable
to be measured. | column | Integer32 | .1.3.6.1.4.1.232.165.5.2.1.1.10 |
| mpduOutputWarningThreshold mandatory Report the User-set threshhold limit for Warning in percentage | column | Integer32 | .1.3.6.1.4.1.232.165.5.2.1.1.11 |
| mpduOutputCriticalThreshold mandatory Report the User-set threshhold limit for Critical in percentage | column | Integer32 | .1.3.6.1.4.1.232.165.5.2.1.1.12 |
| mpduOutputPowerWattHour mandatory Support Billing Grade Energy Metering in Watt-Hour. A value
of -1 will be returned if the power is unable to be calculated. | column | Integer32 | .1.3.6.1.4.1.232.165.5.2.1.1.13 |
| mpduOutputBreakerRating mandatory The rating of each MPDU Output in Ampere. | column | Integer32 | .1.3.6.1.4.1.232.165.5.2.1.1.3 |
| mpduOutputSmartDevice mandatory A smart cord device detected: False, True. StringLength=[5]. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.2.1.1.4 |
| mpduOutputPercentLoad mandatory The MPDU's each output load in percent of rated capacity. Value is
presented in 1/10 of the percentage i.e. 125 is 12.5%. A value
of -1 will be returned if the current is unabl… | column | Integer32 | .1.3.6.1.4.1.232.165.5.2.1.1.5 |
| mpduOutputVoltage mandatory The measured output voltage from the PDU meters in volts. Value is
presented in 1/10 of the Volt i.e. 2095 is 209.5 V. A value
of -1 will be returned if the voltage is unable t… | column | Integer32 | .1.3.6.1.4.1.232.165.5.2.1.1.6 |
| mpduOutputCurrent mandatory The measured output current from the PDU meters in amps. Value is
presented in 1/100 of the Ampere i.e. 175 is 1.75 A. A value
of -1 will be returned if the current is unable t… | column | Integer32 | .1.3.6.1.4.1.232.165.5.2.1.1.7 |
| mpduOutputPowerVA mandatory The total VA load (VI) measured on the PDU in VA. A value
of -1 will be returned if the power is unable to be calculated. | column | Integer32 | .1.3.6.1.4.1.232.165.5.2.1.1.8 |
| mpduOutputPowerWatt mandatory The total power load measured on the PDU in Watts. A value
of -1 will be returned if the power is unable to be calculated. | column | Integer32 | .1.3.6.1.4.1.232.165.5.2.1.1.9 |