hpduOutletStatus
CPQPOWER-MIB ·
.1.3.6.1.4.1.232.165.9.3.1.1.2
Object
The overall status of the breaker: off, on, problem. StringLength=[7].
Context
- MIB
- CPQPOWER-MIB
- OID
.1.3.6.1.4.1.232.165.9.3.1.1.2- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- hpduOutletEntry
- Table
- hpduOutletTable
- Siblings
- 13
Syntax
RFC1213-MIBDisplayString
- Source
- RFC1213-MIBDisplayString
- Base type
OctetString
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| hpduOutletIndex mandatory Index for the hpduOutletEntry table. | column | Integer32 | .1.3.6.1.4.1.232.165.9.3.1.1.1 |
| hpduOutletWarningThreshold mandatory Report the User-set threshhold limit for Warning in percentage | column | Integer32 | .1.3.6.1.4.1.232.165.9.3.1.1.10 |
| hpduOutletCriticalThreshold mandatory Report the User-set threshhold limit for Critical in percentage | column | Integer32 | .1.3.6.1.4.1.232.165.9.3.1.1.11 |
| hpduOutletPowerWattHour mandatory Support Billing Grade Energy Metering in Watt-Hour. A value
of -1 will be returned if the power is unable to be calculated. | column | Integer32 | .1.3.6.1.4.1.232.165.9.3.1.1.12 |
| hpduOutletTotalEnergySince mandatory Display the date and time that starts to accumulate the per Load segment energy in WH.
Date and Time can be set by user on GUI. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.3.1.1.13 |
| hpduOutletEnergyMeteringTotalHours mandatory Total hours of collecting measurement data. A value
of -1 will be returned if the value is unable to be calculated. | column | Integer32 | .1.3.6.1.4.1.232.165.9.3.1.1.14 |
| hpduOutletBreakerRating mandatory The rating of each hpdu Outlet in Ampere. | column | Integer32 | .1.3.6.1.4.1.232.165.9.3.1.1.3 |
| hpduOutletPercentLoad mandatory The hpdu's each Outlet load in percent of rated capacity. Value is
presented in 1/10 of the percentage i.e. 125 is 12.5%. A value
of -1 will be returned if the current is unabl… | column | Integer32 | .1.3.6.1.4.1.232.165.9.3.1.1.4 |
| hpduOutletVoltage mandatory The measured Outlet voltage from the PDU meters in volts. Value is
presented in 1/10 of the Volt i.e. 2095 is 209.5 V. A value
of -1 will be returned if the voltage is unable t… | column | Integer32 | .1.3.6.1.4.1.232.165.9.3.1.1.5 |
| hpduOutletCurrent mandatory The measured Outlet current from the PDU meters in amps. Value is
presented in 1/100 of the Ampere i.e. 175 is 1.75 A. A value
of -1 will be returned if the current is unable t… | column | Integer32 | .1.3.6.1.4.1.232.165.9.3.1.1.6 |
| hpduOutletPowerVA mandatory The total VA load (VI) measured on the PDU in VA. A value
of -1 will be returned if the power is unable to be calculated. | column | Integer32 | .1.3.6.1.4.1.232.165.9.3.1.1.7 |
| hpduOutletPowerWatt mandatory The total power load measured on the PDU in Watts. A value
of -1 will be returned if the power is unable to be calculated. | column | Integer32 | .1.3.6.1.4.1.232.165.9.3.1.1.8 |
| hpduOutletPowerFactor mandatory The power factor is presented in 1/100 of the unit i.e.
98 is 0.98. A value of -1 will be returned if the power factor is unable
to be measured. | column | Integer32 | .1.3.6.1.4.1.232.165.9.3.1.1.9 |