hotAirRecircTempDeltaThresh
CME-MIB ·
.1.3.6.1.4.1.2.3.51.2.2.1.9.5
Object
scalar
mandatory
r/w
Integer32
This object is used to read or change the temperature delta threshold for Hot Air Recirculation detection. Values are enforced to be in the inclusive range between 5.00C and 9.00C and are specified as hundreths of a degree. For example, a value of 659 would equate to a threshold of 6.59 degrees C.
Context
- MIB
- CME-MIB
- OID
.1.3.6.1.4.1.2.3.51.2.2.1.9.5- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- monitorTemp
- Siblings
- 2
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| hotAirRecircMonitoring mandatory If this is enabled, the management module will monitor for Hot Air
Recirculation by detecting non-uniform air temperature(s) that may
be entering the front of the chassis.
… | scalar | Enumeration | .1.3.6.1.4.1.2.3.51.2.2.1.9.3 |
| hotAirRecircStatusTable mandatory Table of hot air recirculation status information. | table | - | .1.3.6.1.4.1.2.3.51.2.2.1.9.7 |