upsLastKnownAlarm
BESTPOWER-MIB ·
.1.3.6.1.4.1.2947.1.8.2
Object
scalar
mandatory
Enumeration
A unique identifier for an alarm condition. This value must remain constant. Value 'noAlarm(37)' will be returned if no Alarm has occured till the point of GET operation.
Context
- MIB
- BESTPOWER-MIB
- OID
.1.3.6.1.4.1.2947.1.8.2- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- upsAlarm
- Siblings
- 3
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | onBattery |
2 | lowRuntime |
3 | nearLowBattery |
4 | lowBattery |
5 | highBattery |
6 | checkBattery |
7 | replaceBattery |
8 | checkInverter |
9 | batteriesDisconnected |
10 | outputOverload |
11 | lowAcOut |
12 | circuitBreakerWarning |
13 | circuitBreakerShdn |
14 | bypassOn |
15 | autoBypass |
16 | siteWiringFault |
17 | checkFan |
18 | highAmbTemp |
19 | highHSTemp |
20 | highXFMRTemp |
21 | highPFMTemp |
22 | probeMissing |
23 | checkPowerSupply |
24 | tapRegulator |
25 | relayFailure |
26 | checkFuse |
27 | checkMOV |
28 | memoryError |
29 | callService |
30 | upsFailed |
31 | userTest |
32 | testInProgress |
33 | diagnosticTestFailed |
34 | ePO |
35 | upsOff |
36 | communicationsLost |
37 | noAlarm |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAlarmsPresent mandatory The present number of active alarm conditions. | scalar | RFC1155-SMIGauge | .1.3.6.1.4.1.2947.1.8.1 |
| upsAlarmTable mandatory A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at… | table | - | .1.3.6.1.4.1.2947.1.8.3 |
| upsWellKnownAlarms | node | - | .1.3.6.1.4.1.2947.1.8.4 |