upsControlEnableGeneratorSensitivity
BESTPOWER-MIB ·
.1.3.6.1.4.1.2947.1.6.5
Object
scalar
mandatory
r/w
Enumeration
Setting this value to a value other than (disable) begins to increase the UPS ability to reject poor line sources for example from a poorly regulated AC generator. The greater the value the greater the tolerance to allow poor line to be used to power the UPS. This control is used to prevent the UPS from using its batteries to create output power and allow an AC generator to supply power to the UPS.
Context
- MIB
- BESTPOWER-MIB
- OID
.1.3.6.1.4.1.2947.1.6.5- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsControl
- Siblings
- 2
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | auto |
2 | g1 |
3 | g2 |
4 | g3 |
5 | g4 |
6 | disable |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsControlTurnOffUPS mandatory Setting this variable to UpsOff(2) causes the UPS to shut off.
When the UPS is in the off state, the UPS will remain off until
the ON/OFF switch is manually toggled.
Se… | scalar | Enumeration | .1.3.6.1.4.1.2947.1.6.1 |
| upsControlActivateUpsScheduling mandatory Setting this variable to On(2) causes the
UPS to activate the scheduling parameters that have been previously
configured within the upsConfigDailyShutdownScheduleTable and the
ups… | scalar | Enumeration | .1.3.6.1.4.1.2947.1.6.4 |