hr40089

ASCO-QEM-72EE2 · .1.3.6.1.4.1.7777.1.7.89

Object

scalar Integer32
MODBUS HR 40089: BIC & ATS Switch Position.
          
40089:00	BTS Position Inputs BTS Norm On
40089:01	BTS Position Inputs BTS Norm Off
40089:02	BTS Position Inputs BTS Emer On
40089:03	BTS Position Inputs BTS Emer Off
40089:04	ATS Position Inputs ATS Norm On
40089:05	ATS Position Inputs ATS Norm Off
40089:06	ATS Position Inputs ATS Emer On
40089:07	ATS Position Inputs ATS Emer Off
40089:08-15	Undefined

Context

MIB
ASCO-QEM-72EE2
OID
.1.3.6.1.4.1.7777.1.7.89
Type
scalar
Access
readonly
Status
current
Parent
bic
Siblings
36

Syntax

Integer32

Values & Constraints

Object Constraints
range: 0-1