chargerStatus
ALGPOWER_v2-MIB ·
.1.3.6.1.4.1.49136.1.2.3
Object
scalar
mandatory
Integer32
Show the status of battery charger:
0 - The battery is not connected in DC UPS;
1 - The battery is voltage incompatible with DC UPS;
2 - The DC UPS is in nobreak mode;
3 - The charger of Battery is in Bulk stage;
4 - The charger of Battery is Absorption stage;
5 - The charger of Battery is Float stage;
6 - The Battery will be disconnected in 30s due to
low voltage and the DC-UPS output will be
turned off.
7 - The Battery is under test
Context
- MIB
- ALGPOWER_v2-MIB
- OID
.1.3.6.1.4.1.49136.1.2.3- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- battery
- Siblings
- 2
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| batteryVoltage mandatory Numeric value of instantaneous voltage of battery bank.
To get the actual value in volt must be divided by 10.
Example:
Read value 240, actual value 24.0V. | scalar | Integer32 | .1.3.6.1.4.1.49136.1.2.1 |
| batteryCurrent mandatory Numeric value of current in Battery bank. Real
value reading in milli ampere.
If the value is negative the Battery bank is provide
energy for the output.
If the value is positive … | scalar | Integer32 | .1.3.6.1.4.1.49136.1.2.2 |