currentIadirection
ACCUENERGY-MIB ·
.1.3.6.1.4.1.39604.1.1.1.1.6.12
Object
This is Current Ia direction. Range: 0: Positive 1: Negative
Context
- MIB
- ACCUENERGY-MIB
- OID
.1.3.6.1.4.1.39604.1.1.1.1.6.12- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- setting
- Siblings
- 19
Syntax
RFC1155-SMIInteger32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| expandedIOModulesConnectStatus | node | - | .1.3.6.1.4.1.39604.1.1.1.1.6.1 |
| demandSlidWindowTime mandatory This is kvarh pulse constant.
Range: 1~6000 | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.10 |
| demandCalculatingMode mandatory This is Demand calculating mode.
Range: 1:sliding window, 2:thermal | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.11 |
| currentIbdirection mandatory This is Current Ib direction.
Range: 0: Positive 1: Negative | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.13 |
| currentIcdirection mandatory This is Current Ic direction.
Range: 0: Positive 1: Negative | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.14 |
| varAndPFConvention mandatory This is VAR/PF convention.
Range: 0: IEC, 1: IEEE | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.15 |
| energyCalculatingMode mandatory This is Energy calculating mode.
Range: 0: fundamental 1: full-wave | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.16 |
| reactivePowerMeasuringMode mandatory This is Reactive power measuring mode.
Range: 0: real, 1: general | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.17 |
| energyDisplayMode mandatory This is Energy display mode.
Range: 0: primary, 1: secondary | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.18 |
| basicParameterMode mandatory This is Basic parameter mode.
Range: 0:secondary; 1:primary | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.19 |
| voltageInputWiringType mandatory This is Voltage input wiring type.
Range: 0:3LN,1:2LN,2:2LL,3:3LL | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.2 |
| runtime mandatory This is Run time.
Relationship(Primary&Secondary Mode): T=Rx/100
Range: 0~999999999 | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.20 |
| currentInputWiringType mandatory This is current input wiring type.
Range: 0:3CT,1:1CT,2:2CTL | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.3 |
| pt1 mandatory This is PT1.
Range: 50.0~500000.0 | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.4 |
| pt2 mandatory This is PT2.
Range: 50.0~400.0 | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.5 |
| ct1 mandatory This is CT1.
Range: 1~50000 | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.6 |
| ct2 mandatory This is CT2.
Range: 1,5 | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.7 |
| kWhPulseConstant mandatory This is kWh pulse constant.
Range: 1~6000 | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.8 |
| kvarhPulseConstant mandatory This is kvarh pulse constant.
Range: 1~6000 | scalar | RFC1155-SMIInteger32 | .1.3.6.1.4.1.39604.1.1.1.1.6.9 |