UPS-MIB
The MIB module to describe Uninterruptible Power
Supplies.
- Source file
UPS-MIB- Last revised
- Identity
upsMIB- Base OID
1.3.6.1.2.1.33
Imported Objects
| SNMPv2-CONF | MODULE-COMPLIANCE (no object page) OBJECT-GROUP (no object page) |
| SNMPv2-SMI | Counter32 Gauge32 Integer32 mib-2 MODULE-IDENTITY (no object page) NOTIFICATION-TYPE (no object page) OBJECT-IDENTITY (no object page) OBJECT-TYPE (no object page) |
| SNMPv2-TC | AutonomousType DisplayString TestAndIncr TEXTUAL-CONVENTION (no object page) TimeInterval TimeStamp |
Net-SNMP examples using the liebert MIB directory Show commands
These commands use the standard Observium installation path and load the selected MIB variant before the RFC and Net-SNMP directories.
Translate the module identity
/usr/bin/snmptranslate -Pud -Ir -On -m 'UPS-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'UPS-MIB::upsMIB'
Walk the MIB subtree
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'UPS-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'UPS-MIB::upsMIB'
Objects (116)
Showing 116 of 116 objects
Object legend
Object type
Icons distinguish tables, entry rows, columns, scalars, and structural nodes.
SNMPv2-TCTruthValue
Syntax
Blue badges identify the value syntax. Connected badges read as defining module and convention.
IF-MIBifIndex
Table index
Green identifies an index object; yellow names its module when the index is defined elsewhere.
r/w
deprecated
obsolete
Access and status
r/w means read-write. Grey labels mark definitions retained for compatibility.
OBS ✓
Observium use
The indicator appears only when Observium directly references that object.
ifOperStatus
.1.3.6.1.2.1…
Names and OIDs
Object names link to their detail pages. Hover or focus a linked name or badge for available definition details.
.1.3.6.1.2.1.33 |
||
.1.3.6.1.2.1.33.1 |
||
.1.3.6.1.2.1.33.1.1 |
||
|
OctetString
|
.1.3.6.1.2.1.33.1.1.1 |
|
|
OctetString
|
.1.3.6.1.2.1.33.1.1.2 |
|
|
OctetString
|
.1.3.6.1.2.1.33.1.1.3 |
|
|
OctetString
|
.1.3.6.1.2.1.33.1.1.4 |
|
|
|
OctetString
|
.1.3.6.1.2.1.33.1.1.5 |
|
OctetString
|
.1.3.6.1.2.1.33.1.1.6 |
|
.1.3.6.1.2.1.33.1.2 |
||
|
Enumeration
|
.1.3.6.1.2.1.33.1.2.1 |
|
|
secondsNonNegativeInteger
|
.1.3.6.1.2.1.33.1.2.2 |
|
|
minutesPositiveInteger
|
.1.3.6.1.2.1.33.1.2.3 |
|
|
percentInteger32
|
.1.3.6.1.2.1.33.1.2.4 |
|
|
0.1 Volt DCNonNegativeInteger
|
.1.3.6.1.2.1.33.1.2.5 |
|
|
0.1 Amp DCSNMPv2-SMIInteger32
|
.1.3.6.1.2.1.33.1.2.6 |
|
|
degrees CentigradeSNMPv2-SMIInteger32
|
.1.3.6.1.2.1.33.1.2.7 |
|
.1.3.6.1.2.1.33.1.3 |
||
.1.3.6.1.2.1.33.1.3.1 |
||
.1.3.6.1.2.1.33.1.3.2 |
||
.1.3.6.1.2.1.33.1.3.3 |
||
.1.3.6.1.2.1.33.1.3.3.1 |
||
.1.3.6.1.2.1.33.1.3.3.1.1 |
||
|
0.1 HertzNonNegativeInteger
|
.1.3.6.1.2.1.33.1.3.3.1.2 |
|
|
RMS VoltsNonNegativeInteger
|
.1.3.6.1.2.1.33.1.3.3.1.3 |
|
|
0.1 RMS AmpNonNegativeInteger
|
.1.3.6.1.2.1.33.1.3.3.1.4 |
|
|
WattsNonNegativeInteger
|
.1.3.6.1.2.1.33.1.3.3.1.5 |
|
.1.3.6.1.2.1.33.1.4 |
||
|
Enumeration
|
.1.3.6.1.2.1.33.1.4.1 |
|
|
0.1 HertzNonNegativeInteger
|
.1.3.6.1.2.1.33.1.4.2 |
|
.1.3.6.1.2.1.33.1.4.3 |
||
.1.3.6.1.2.1.33.1.4.4 |
||
.1.3.6.1.2.1.33.1.4.4.1 |
||
.1.3.6.1.2.1.33.1.4.4.1.1 |
||
|
RMS VoltsNonNegativeInteger
|
.1.3.6.1.2.1.33.1.4.4.1.2 |
|
|
0.1 RMS AmpNonNegativeInteger
|
.1.3.6.1.2.1.33.1.4.4.1.3 |
|
|
WattsNonNegativeInteger
|
.1.3.6.1.2.1.33.1.4.4.1.4 |
|
|
percentInteger32
|
.1.3.6.1.2.1.33.1.4.4.1.5 |
|
.1.3.6.1.2.1.33.1.5 |
||
|
0.1 HertzNonNegativeInteger
|
.1.3.6.1.2.1.33.1.5.1 |
|
.1.3.6.1.2.1.33.1.5.2 |
||
.1.3.6.1.2.1.33.1.5.3 |
||
.1.3.6.1.2.1.33.1.5.3.1 |
||
.1.3.6.1.2.1.33.1.5.3.1.1 |
||
|
RMS VoltsNonNegativeInteger
|
.1.3.6.1.2.1.33.1.5.3.1.2 |
|
|
0.1 RMS AmpNonNegativeInteger
|
.1.3.6.1.2.1.33.1.5.3.1.3 |
|
|
WattsNonNegativeInteger
|
.1.3.6.1.2.1.33.1.5.3.1.4 |
|
.1.3.6.1.2.1.33.1.6 |
||
.1.3.6.1.2.1.33.1.6.1 |
||
.1.3.6.1.2.1.33.1.6.2 |
||
.1.3.6.1.2.1.33.1.6.2.1 |
||
.1.3.6.1.2.1.33.1.6.2.1.1 |
||
.1.3.6.1.2.1.33.1.6.2.1.2 |
||
.1.3.6.1.2.1.33.1.6.2.1.3 |
||
.1.3.6.1.2.1.33.1.6.3 |
||
.1.3.6.1.2.1.33.1.6.3.1 |
||
.1.3.6.1.2.1.33.1.6.3.10 |
||
.1.3.6.1.2.1.33.1.6.3.11 |
||
.1.3.6.1.2.1.33.1.6.3.12 |
||
.1.3.6.1.2.1.33.1.6.3.13 |
||
.1.3.6.1.2.1.33.1.6.3.14 |
||
.1.3.6.1.2.1.33.1.6.3.15 |
||
.1.3.6.1.2.1.33.1.6.3.16 |
||
.1.3.6.1.2.1.33.1.6.3.17 |
||
.1.3.6.1.2.1.33.1.6.3.18 |
||
.1.3.6.1.2.1.33.1.6.3.19 |
||
.1.3.6.1.2.1.33.1.6.3.2 |
||
.1.3.6.1.2.1.33.1.6.3.20 |
||
.1.3.6.1.2.1.33.1.6.3.21 |
||
.1.3.6.1.2.1.33.1.6.3.22 |
||
.1.3.6.1.2.1.33.1.6.3.23 |
||
.1.3.6.1.2.1.33.1.6.3.24 |
||
.1.3.6.1.2.1.33.1.6.3.3 |
||
.1.3.6.1.2.1.33.1.6.3.4 |
||
.1.3.6.1.2.1.33.1.6.3.5 |
||
.1.3.6.1.2.1.33.1.6.3.6 |
||
.1.3.6.1.2.1.33.1.6.3.7 |
||
.1.3.6.1.2.1.33.1.6.3.8 |
||
.1.3.6.1.2.1.33.1.6.3.9 |
||
.1.3.6.1.2.1.33.1.7 |
||
|
|
ObjectIdentifier
|
.1.3.6.1.2.1.33.1.7.1 |
|
|
.1.3.6.1.2.1.33.1.7.2 |
|
|
Enumeration
|
.1.3.6.1.2.1.33.1.7.3 |
|
|
OctetString
|
.1.3.6.1.2.1.33.1.7.4 |
|
.1.3.6.1.2.1.33.1.7.5 |
||
.1.3.6.1.2.1.33.1.7.6 |
||
.1.3.6.1.2.1.33.1.7.7 |
||
.1.3.6.1.2.1.33.1.7.7.1 |
||
.1.3.6.1.2.1.33.1.7.7.2 |
||
.1.3.6.1.2.1.33.1.7.7.3 |
||
.1.3.6.1.2.1.33.1.7.7.4 |
||
.1.3.6.1.2.1.33.1.7.7.5 |
||
.1.3.6.1.2.1.33.1.8 |
||
|
|
Enumeration
|
.1.3.6.1.2.1.33.1.8.1 |
|
secondsInteger32
|
.1.3.6.1.2.1.33.1.8.2 |
|
|
secondsInteger32
|
.1.3.6.1.2.1.33.1.8.3 |
|
|
secondsInteger32
|
.1.3.6.1.2.1.33.1.8.4 |
|
|
|
Enumeration
|
.1.3.6.1.2.1.33.1.8.5 |
.1.3.6.1.2.1.33.1.9 |
||
|
RMS VoltsNonNegativeInteger
|
.1.3.6.1.2.1.33.1.9.1 |
|
|
RMS VoltsNonNegativeInteger
|
.1.3.6.1.2.1.33.1.9.10 |
|
|
0.1 HertzNonNegativeInteger
|
.1.3.6.1.2.1.33.1.9.2 |
|
|
RMS VoltsNonNegativeInteger
|
.1.3.6.1.2.1.33.1.9.3 |
|
|
0.1 HertzNonNegativeInteger
|
.1.3.6.1.2.1.33.1.9.4 |
|
|
Volt-AmpsNonNegativeInteger
|
.1.3.6.1.2.1.33.1.9.5 |
|
|
WattsNonNegativeInteger
|
.1.3.6.1.2.1.33.1.9.6 |
|
|
minutesNonNegativeInteger
|
.1.3.6.1.2.1.33.1.9.7 |
|
|
Enumeration
|
.1.3.6.1.2.1.33.1.9.8 |
|
|
RMS VoltsNonNegativeInteger
|
.1.3.6.1.2.1.33.1.9.9 |
|
.1.3.6.1.2.1.33.2 |
||
.1.3.6.1.2.1.33.3 |
||
.1.3.6.1.2.1.33.3.1 |
||
.1.3.6.1.2.1.33.3.2 |
||
.1.3.6.1.2.1.33.3.2.1 |
||
.1.3.6.1.2.1.33.3.2.2 |
||
.1.3.6.1.2.1.33.3.2.3 |
Dependencies (3) 3 direct Show tree and compile order Hide dependency details
Each imported module is resolved in the importing module's source directory first, then through the normal default-variant rules.
Dependency tree
Dependency-first compile order
- SNMPv2-SMIrfc
- SNMPv2-CONFrfc
- SNMPv2-TCrfc
- UPS-MIBliebertselected
Type Definitions (2)
| Integer32 |
range: 0..2147483647 |
|
| Integer32 |
range: 1..2147483647 |
Conformance Groups (25)
|
upsIdentManufacturer upsIdentModel upsIdentAgentSoftwareVersion upsIdentName upsIdentAttachedDevices
The upsSubsetIdentGroup defines objects which are
common across all UPSs which meet subset compliance. Most devices which conform to the upsSubsetIdentGroup will provide access to these objects via a proxy agent. If the proxy agent is compatible with multiple UPS types, configuration of the proxy agent will require specifying some of these values, either individually, or as a group (perhaps through a table lookup mechanism based on the UPS model number). |
.1.3.6.1.2.1.33.3.2.1.1
|
|
|
The upsSubsetBatteryGroup defines the objects that
are common to battery groups of two-contact UPSs. |
.1.3.6.1.2.1.33.3.2.1.2
|
|
|
The upsSubsetInputGroup defines the objects that are
common to the Input groups of two-contact UPSs. |
.1.3.6.1.2.1.33.3.2.1.3
|
|
|
The upsSubsetOutputGroup defines the objects that are
common to the Output groups of two-contact UPSs. |
.1.3.6.1.2.1.33.3.2.1.4
|
|
|
The upsSubsetAlarmGroup defines the objects that are
common to the Alarm groups of two-contact UPSs. |
.1.3.6.1.2.1.33.3.2.1.6
|
|
|
The upsSubsetControlGroup defines the objects that
are common to the Control groups of two-contact UPSs. |
.1.3.6.1.2.1.33.3.2.1.8
|
|
|
upsConfigInputVoltage upsConfigInputFreq upsConfigOutputVoltage upsConfigOutputFreq upsConfigOutputVA upsConfigOutputPower
The upsSubsetConfigGroup defines the objects that are
common to the Config groups of two-contact UPSs. |
.1.3.6.1.2.1.33.3.2.1.9
|
|
|
upsIdentManufacturer upsIdentModel upsIdentUPSSoftwareVersion upsIdentAgentSoftwareVersion upsIdentName
The upsBasicIdentGroup defines objects which are
common to the Ident group of compliant UPSs which support basic functions. |
.1.3.6.1.2.1.33.3.2.2.1
|
|
|
The upsBasicBatteryGroup defines the objects that are
common to the battery groups of compliant UPSs which support basic functions. |
.1.3.6.1.2.1.33.3.2.2.2
|
|
|
The upsBasicInputGroup defines the objects that are
common to the Input groups of compliant UPSs which support basic functions. |
.1.3.6.1.2.1.33.3.2.2.3
|
|
|
The upsBasicOutputGroup defines the objects that are
common to the Output groups of compliant UPSs which support basic functions. |
.1.3.6.1.2.1.33.3.2.2.4
|
|
|
The upsBasicBypassGroup defines the objects that are
common to the Bypass groups of compliant UPSs which support basic functions. |
.1.3.6.1.2.1.33.3.2.2.5
|
|
|
The upsBasicAlarmGroup defines the objects that are
common to the Alarm groups of compliant UPSs which support basic functions. |
.1.3.6.1.2.1.33.3.2.2.6
|
|
|
upsTestId upsTestSpinLock upsTestResultsSummary upsTestResultsDetail upsTestStartTime upsTestElapsedTime
The upsBasicTestGroup defines the objects that are
common to the Test groups of compliant UPSs which support basic functions. |
.1.3.6.1.2.1.33.3.2.2.7
|
|
|
The upsBasicControlGroup defines the objects that are
common to the Control groups of compliant UPSs which support basic functions. |
.1.3.6.1.2.1.33.3.2.2.8
|
|
|
upsConfigInputVoltage upsConfigInputFreq upsConfigOutputVoltage upsConfigOutputFreq upsConfigOutputVA upsConfigOutputPower upsConfigLowBattTime upsConfigAudibleStatus
The upsBasicConfigGroup defines the objects that are
common to the Config groups of UPSs which support basic functions. |
.1.3.6.1.2.1.33.3.2.2.9
|
|
|
upsIdentManufacturer upsIdentModel upsIdentUPSSoftwareVersion upsIdentAgentSoftwareVersion upsIdentName upsIdentAttachedDevices
The upsFullIdentGroup defines objects which are
common to the Ident group of fully compliant UPSs. |
.1.3.6.1.2.1.33.3.2.3.1
|
|
|
The upsFullBatteryGroup defines the objects that are
common to the battery groups of fully compliant UPSs. |
.1.3.6.1.2.1.33.3.2.3.2
|
|
|
The upsFullInputGroup defines the objects that are
common to the Input groups of fully compliant UPSs. |
.1.3.6.1.2.1.33.3.2.3.3
|
|
|
upsOutputSource upsOutputFrequency upsOutputNumLines upsOutputVoltage upsOutputCurrent upsOutputPower upsOutputPercentLoad
The upsFullOutputGroup defines the objects that are
common to the Output groups of fully compliant UPSs. |
.1.3.6.1.2.1.33.3.2.3.4
|
|
|
The upsFullBypassGroup defines the objects that are
common to the Bypass groups of fully compliant UPSs. |
.1.3.6.1.2.1.33.3.2.3.5
|
|
|
The upsFullAlarmGroup defines the objects that are
common to the Alarm groups of fully compliant UPSs. |
.1.3.6.1.2.1.33.3.2.3.6
|
|
|
upsTestId upsTestSpinLock upsTestResultsSummary upsTestResultsDetail upsTestStartTime upsTestElapsedTime
The upsFullTestGroup defines the objects that are
common to the Test groups of fully compliant UPSs. |
.1.3.6.1.2.1.33.3.2.3.7
|
|
|
The upsFullControlGroup defines the objects that are
common to the Control groups of fully compliant UPSs. |
.1.3.6.1.2.1.33.3.2.3.8
|
|
|
upsConfigInputVoltage upsConfigInputFreq upsConfigOutputVoltage upsConfigOutputFreq upsConfigOutputVA upsConfigOutputPower upsConfigLowBattTime upsConfigAudibleStatus
The upsFullConfigGroup defines the objects that are
common to the Config groups of fully compliant UPSs. |
.1.3.6.1.2.1.33.3.2.3.9
|
Compliance Statements (3)
OID
.1.3.6.1.2.1.33.3.1.1The compliance statement for UPSs that only support
the two-contact communication protocol.
the two-contact communication protocol.
Required groups
| mandatory | upsSubsetIdentGroup | |
| mandatory | upsSubsetBatteryGroup | |
| mandatory | upsSubsetInputGroup | |
| mandatory | upsSubsetOutputGroup | |
| mandatory | upsSubsetAlarmGroup | |
| mandatory | upsSubsetControlGroup | |
| mandatory | upsSubsetConfigGroup |
Object refinements
| Object | Access | Syntax | Description |
|---|---|---|---|
| upsBatteryStatus |
Enumeration
batteryNormal(2), batteryLow(3)
|
Support of the values unknown(1) and batteryDepleted(4) is not required. |
|
| upsAlarmDescr | Support of all `well known' alarm types is not required. The well known alarm types which must be supported are: upsAlarmOnBattery, upsAlarmLowBattery, upsAlarmInputBad, upsAlarmUpsOutputOff, upsAlarmUpsSystemOff, and upsAlarmTestInProgress. |
||
| upsOutputSource |
Enumeration
normal(3), battery(5)
|
Support of the values other(1), none(2), bypass(4), booster(6) and reducer(7) is not required. |
|
| upsShutdownType | readonly | Read-write access is not required, i.e., compliant systems need not support more than one shutdown type. |
|
| upsAutoRestart | readonly | Read-write access is not required, i.e., compliant systems need not support more than one restart type. |
|
| upsConfigInputVoltage | readonly | Read-write access is not required. | |
| upsConfigInputFreq | readonly | Read-write access is not required. | |
| upsConfigOutputVoltage | readonly | Read-write access is not required. | |
| upsConfigOutputFreq | readonly | Read-write access is not required. |
OID
.1.3.6.1.2.1.33.3.1.2The compliance statement for UPSs that support
full-featured functions, such as control.
full-featured functions, such as control.
Required groups
| mandatory | upsBasicIdentGroup | |
| mandatory | upsBasicBatteryGroup | |
| mandatory | upsBasicInputGroup | |
| mandatory | upsBasicOutputGroup | |
| mandatory | upsBasicAlarmGroup | |
| mandatory | upsBasicTestGroup | |
| mandatory | upsBasicControlGroup | |
| mandatory | upsBasicConfigGroup | |
| optional | upsBasicBypassGroup |
The upsBasicBypassGroup is only required for UPSs that have a Bypass present. |
Object refinements
| Object | Access | Syntax | Description |
|---|---|---|---|
| upsAlarmDescr | Support of all `well known' alarm types is not required. The well known alarm types which must be supported are: upsAlarmOnBattery, upsAlarmLowBattery, upsAlarmDepletedBattery, upsAlarmTempBad, upsAlarmInputBad, upsAlarmOutputOverload, upsAlarmOnBypass, upsAlarmBypassBad, upsAlarmOutputOffAsRequested, upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff, upsAlarmUpsSystemOff, upsAlarmGeneralFault, upsAlarmDiagnosticTestFailed, upsAlarmCommunicationsLost, upsAlarmShutdownPending, and upsAlarmTestInProgress. |
||
| upsTestId | Support of all `well known' test types is not required. If no tests are supported, then the only well known test type which must be supported is upsTestNoTestsInitiated. |
||
| upsOutputSource |
Enumeration
normal(3), battery(5)
|
Support of the values other(1), none(2), bypass(4), booster(6) and reducer(7) is not required. |
|
| upsShutdownType | readonly | Read-write access is not required, i.e., compliant systems need not support more than one shutdown type. |
|
| upsAutoRestart | readonly | Read-write access is not required, i.e., compliant systems need not support more than one restart type. |
|
| upsConfigInputVoltage | readonly | Read-write access is not required. | |
| upsConfigInputFreq | readonly | Read-write access is not required. | |
| upsConfigOutputVoltage | readonly | Read-write access is not required. | |
| upsConfigOutputFreq | readonly | Read-write access is not required. | |
| upsConfigLowBattTime | Implementation of all possible values may be onerous for some systems. Consequently, not all possible values must be supported. However, at least two different manufacturer-selected values must be supported. |
OID
.1.3.6.1.2.1.33.3.1.3The compliance statement for UPSs that support
advanced full-featured functions.
advanced full-featured functions.
Required groups
| mandatory | upsFullIdentGroup | |
| mandatory | upsFullBatteryGroup | |
| mandatory | upsFullInputGroup | |
| mandatory | upsFullOutputGroup | |
| mandatory | upsFullAlarmGroup | |
| mandatory | upsFullTestGroup | |
| mandatory | upsFullControlGroup | |
| mandatory | upsFullConfigGroup | |
| optional | upsFullBypassGroup |
The upsFullBypassGroup is only required for UPSs that have a Bypass present. |
Object refinements
| Object | Access | Syntax | Description |
|---|---|---|---|
| upsAlarmDescr | Support of all `well known' alarm types is not required. The well known alarm types which must be supported are: upsAlarmBatteryBad, upsAlarmOnBattery, upsAlarmLowBattery, upsAlarmDepletedBattery, upsAlarmTempBad, upsAlarmInputBad, upsAlarmOnBypass, upsAlarmBypassBad, upsAlarmOutputOffAsRequested, upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff, upsAlarmUpsSystemOff, upsAlarmGeneralFault, upsAlarmDiagnosticTestFailed, upsAlarmCommunicationsLost, upsAlarmShutdownPending, and upsAlarmTestInProgress. |
||
| upsTestId | Support of all `well known' test types is not required. The well known test types which must be supported are: upsTestNoTestsInitiated, upsTestGeneralSystemsTest, and upsTestQuickBatteryTest. |
||
| upsOutputSource |
Enumeration
normal(3), battery(5)
|
Support of the values other(1), none(2), bypass(4), booster(6) and reducer(7) is not required. |
|
| upsShutdownType | readonly | Read-write access is not required, i.e., compliant systems need not support more than one shutdown type. |
|
| upsAutoRestart | readonly | Read-write access is not required, i.e., compliant systems need not support more than one restart type. |
|
| upsConfigInputVoltage | readonly | Read-write access is not required. | |
| upsConfigInputFreq | readonly | Read-write access is not required. | |
| upsConfigOutputVoltage | readonly | Read-write access is not required. | |
| upsConfigOutputFreq | readonly | Read-write access is not required. | |
| upsConfigLowBattTime | Implementation of all possible values may be onerous for some systems. Consequently, not all possible values must be supported. However, at least two different manufacturer-selected values must be supported. |
Notifications / Traps (4)
| Name | OID | Description |
|---|---|---|
.1.3.6.1.2.1.33.2.1 |
The UPS is operating on battery power. This trap is
persistent and is resent at one minute intervals until the UPS either turns off or is no longer running on battery. |
|
.1.3.6.1.2.1.33.2.2 |
This trap is sent upon completion of a UPS diagnostic
test. |
|
.1.3.6.1.2.1.33.2.3 |
This trap is sent each time an alarm is inserted into
to the alarm table. It is sent on the insertion of all alarms except for upsAlarmOnBattery and upsAlarmTestInProgress. |
|
.1.3.6.1.2.1.33.2.4 |
This trap is sent each time an alarm is removed from
the alarm table. It is sent on the removal of all alarms except for upsAlarmTestInProgress. |