PDU-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
2
Rows
2
Columns
25

outletTable

table
.1.3.6.1.4.1.13742.2.1.2.2 · 1 row entry · 12 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk outletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PDU-MIB::outletTable'
A list of outlet entries. The number of
entries is given by the value of ifNumber.
outletEntry row .1.3.6.1.4.1.13742.2.1.2.2.1
An outlet entry containing objects at the
for a particular outlet.
Indexes
Column Syntax OID
A unique value for each outlet. Its value
ranges between 1 and the value of outletNumber.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.1
A textual string containing information
about the outlet.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.13742.2.1.2.2.1.2
A value for each outlet which describes the
operational state of the outlet. It is also
used to set the operational state of the outlet
Enumerationr/w
Enumerated Values:
-1error
0off
1on
2cycling
.1.3.6.1.4.1.13742.2.1.2.2.1.3
A unique value for the RMS current sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.4
A unique value for the RMS phase sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.5
A unique value for the max. RMS current sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.6
A unique value for the true RMS power sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.7
A unique value for the apparent RMS power sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.8
A unique value for the max. true RMS power sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.9
A unique value for the average real RMS power sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.10
A unique value for the RMS voltage sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.11
A unique value for the frequency sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.12

sensorTable

table
.1.3.6.1.4.1.13742.2.1.3.2 · 1 row entry · 13 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk sensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PDU-MIB::sensorTable'
A list of sensors of the pdu. The number of
entries is given by the value of sensorNumber.
sensorEntry row .1.3.6.1.4.1.13742.2.1.3.2.1
An sensor entry containing objects at the
for a particular sensor.
Indexes
Column Syntax OID
A unique value for each sensor. Its value
ranges between 1 and may exceed the value
of sensorNumber.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.3.2.1.1
A textual string containing information
about the sensor.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.13742.2.1.3.2.1.2
The type of the sensor.
Enumeration
Enumerated Values:
0receptacle-rms-current
1receptacle-rms-phase
2receptacle-max-rms-current
3receptacle-true-rms-power
4receptacle-apparent-rms-power
5receptacle-max-true-rms-power
6receptacle-average-real-rms-power
192power-branch-rms-voltage
193power-branch-frequency
194power-branch-temperature
195power-branch-rms-current
197environmental-temp-3
198environmental-temp-2
199environmental-temp-1
206environmental-humidity-2
207environmental-humidity-1
240unit-circuit-break-0
241unit-circuit-break-1
242unit-rms-current
243unit-max-rms-current
244unit-temp
245unit-true-power
246unit-apparent-power
247unit-rms-voltage
.1.3.6.1.4.1.13742.2.1.3.2.1.3
The value the sensor delivers. This value is
provided as ASN_OPAQUE_FLOAT type. In case of
an error or unavailability NaN is returned
SNMPv2-SMIOpaque .1.3.6.1.4.1.13742.2.1.3.2.1.4
A string that containes the unit of the value.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.13742.2.1.3.2.1.5
To state of the sensor.
Enumeration
Enumerated Values:
-1unavailable
0ok
1below-lower-non-critical
2above-upper-non-critical
3below-lower-critical
4above-upper-critical
5below-lower-non-recoverable
6above-upper-non-recoverable
.1.3.6.1.4.1.13742.2.1.3.2.1.6
A unique value for the outlet the sensor
is associated to, if any. This is also an
index into the outlets table outletTable.
An value of 0 indicates no associated outlet.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.3.2.1.7
The value for the lower non-critical
threshold of the sensor. This value is
provided as ASN_OPAQUE_FLOAT type. In case of
an error or unavailability NaN is returned.
Setting this value is possible via:
ASN_INTEGER, ASN_…
SNMPv2-SMIOpaquer/w .1.3.6.1.4.1.13742.2.1.3.2.1.8
The value for the upper non-critical
threshold of the sensor. This value is
provided as ASN_OPAQUE_FLOAT type. In case of
an error or unavailability NaN is returned.
Setting this value is possible via:
ASN_INTEGER, ASN_…
SNMPv2-SMIOpaquer/w .1.3.6.1.4.1.13742.2.1.3.2.1.9
The value for the lower critical
threshold of the sensor. This value is
provided as ASN_OPAQUE_FLOAT type. In case of
an error or unavailability NaN is returned.
Setting this value is possible via:
ASN_INTEGER, ASN_OCTE…
SNMPv2-SMIOpaquer/w .1.3.6.1.4.1.13742.2.1.3.2.1.10
The value for the upper critical
threshold of the sensor. This value is
provided as ASN_OPAQUE_FLOAT type. In case of
an error or unavailability NaN is returned.
Setting this value is possible via:
ASN_INTEGER, ASN_OCTE…
SNMPv2-SMIOpaquer/w .1.3.6.1.4.1.13742.2.1.3.2.1.11
The value for the lower non-recoverable
threshold of the sensor. This value is
provided as ASN_OPAQUE_FLOAT type. In case of
an error or unavailability NaN is returned.
Setting this value is possible via:
ASN_INTEGER, A…
SNMPv2-SMIOpaquer/w .1.3.6.1.4.1.13742.2.1.3.2.1.12
The value for the upper non-recoverable
threshold of the sensor. This value is
provided as ASN_OPAQUE_FLOAT type. In case of
an error or unavailability NaN is returned.
Setting this value is possible via:
ASN_INTEGER, A…
SNMPv2-SMIOpaquer/w .1.3.6.1.4.1.13742.2.1.3.2.1.13