WebGraph-Thermometer-US-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
7
Rows
7
Columns
42
.1.3.6.1.4.1.5040.1.2.8.1.2
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-US-MIB::wtWebioAn1GraphSensorTable'
List of sensors.
Temperature sensor numbers.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebioAn1GraphSensorNomandatory Temperature sensor number. | Integer32 Constraints: range: 1-1 | .1.3.6.1.4.1.5040.1.2.8.1.2.1.1 |
.1.3.6.1.4.1.5040.1.2.8.1.3
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphTempValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-US-MIB::wtWebioAn1GraphTempValueTable'
List of temperature values corresponding to the channel numbers.
Temperatures of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebioAn1GraphTempValuemandatory Temperature value of the sensor, ASCII, 5 characters in length. | OctetString Constraints: range: 5-5 | .1.3.6.1.4.1.5040.1.2.8.1.3.1.1 |
.1.3.6.1.4.1.5040.1.2.8.1.4
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphBinaryTempValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-US-MIB::wtWebioAn1GraphBinaryTempValueTable'
List of binary temperature values corresponding to the channel numbers.
Binary temperature values of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebioAn1GraphBinaryTempValuemandatory Binary temperature value of the sensor in 1/10 degrees Celsius,signed number, 0x7FFF indicates an invalid measured value. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.5040.1.2.8.1.4.1.1 |
.1.3.6.1.4.1.5040.1.2.8.3.1.4.4
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphSensorColorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-US-MIB::wtWebioAn1GraphSensorColorTable'
List of sensor colors for the praphical presentation.
Index numbers of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebioAn1GraphSensorColormandatory Color of the sensors at the praphical presention. | OctetStringr/w Constraints: range: 3-3 | .1.3.6.1.4.1.5040.1.2.8.3.1.4.4.1.1 |
.1.3.6.1.4.1.5040.1.2.8.3.1.5.2
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphAlarmIfTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-US-MIB::wtWebioAn1GraphAlarmIfTable'
List of alarm indices.
Numbers of the alarms.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebioAn1GraphAlarmNomandatory Alarm number. | Integer32 Constraints: range: 1-8 | .1.3.6.1.4.1.5040.1.2.8.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.8.3.1.5.3
·
1 row entry
·
30 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-US-MIB::wtWebioAn1GraphAlarmTable'
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebioAn1GraphAlarmTriggermandatory Binary coded trigger conditions:Octet 1: unused Octet 2: unused Octet 3: Bit 0: Timer Bit 1: ColdStart Bit 2: WarmStart Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2: Sensor 3 Bit 3: Sensor 4 B… | OctetStringr/w Constraints: range: 4-4 | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.1 |
wtWebioAn1GraphAlarmMinmandatory Minimum temperature in degrees with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.2 |
wtWebioAn1GraphAlarmMaxmandatory Maximum temperature in degrees with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.3 |
wtWebioAn1GraphAlarmHysteresismandatory Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.), in degrees with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.4 |
wtWebioAn1GraphAlarmDelaymandatory Alarm will be delayed by setting this time while stable alarm condition occur (time in minutes). | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.5 |
wtWebioAn1GraphAlarmIntervalmandatory Send interval for alarm messages. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.6 |
wtWebioAn1GraphAlarmEnablemandatory Binary coded alarm enable:Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable | OctetStringr/w Constraints: range: 4-4 | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.7 |
wtWebioAn1GraphAlarmEMailAddrmandatory E-Mail address for sending the alarm mail to. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.8 |
wtWebioAn1GraphAlarmMailSubjectmandatory Subject line for alarm mail. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.9 |
wtWebioAn1GraphAlarmMailTextmandatory Alarm mail text: <Tn> provides the current temperature; n = 1..8.<Z> provides the current time. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.10 |
wtWebioAn1GraphAlarmManagerIPmandatory Name or IP address of the SNMP Manager which accepts the trap. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.11 |
wtWebioAn1GraphAlarmTrapTextmandatory This text is sent in the trap body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.12 |
wtWebioAn1GraphAlarmMailOptionsmandatory Binary coded options:Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Thermo.csv Enable Bit 1-7: unused | OctetStringr/w Constraints: range: 4-4 | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.13 |
wtWebioAn1GraphAlarmTcpIpAddrmandatory Name or IP address of the TCP server which accepts the trap. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.14 |
wtWebioAn1GraphAlarmTcpPortmandatory Port number of the TCP server which accepts the trap. | Integer32r/w Constraints: range: 1-65535 | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.15 |
wtWebioAn1GraphAlarmTcpTextmandatory This text is sent in the TCP trap body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.16 |
wtWebioAn1GraphAlarmClearMailSubjectmandatory Subject line for alarm clear mail. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.17 |
wtWebioAn1GraphAlarmClearMailTextmandatory Alarm clear mail text: <Tn> provides the current temperature; n = 1..8. <Z> provides the current time. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.18 |
wtWebioAn1GraphAlarmClearTrapTextmandatory This text is sent in the trap body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.19 |
wtWebioAn1GraphAlarmClearTcpTextmandatory This text is sent in the TCP trap body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.20 |
wtWebioAn1GraphAlarmSyslogIpAddrmandatory IP address of the syslog server to which the Webio device should send syslog messages. | RFC1155-SMIIpAddressr/w Type Constraints: range: 4 | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.21 |
wtWebioAn1GraphAlarmSyslogPortmandatory Port number of the syslog server to which the Webio device should send syslog messages. | Integer32r/w Constraints: range: 1-65535 | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.22 |
wtWebioAn1GraphAlarmSyslogTextmandatory Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.This text appears in the following syslog message body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.23 |
wtWebioAn1GraphAlarmSyslogClearTextmandatory Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.This text appears in the following syslog message body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.24 |
wtWebioAn1GraphAlarmFtpDataPortmandatory Local data port: 1..65535 or AUTO: the next free port will be assigned. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.25 |
wtWebioAn1GraphAlarmFtpFileNamemandatory Name of the file including path informations. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.26 |
wtWebioAn1GraphAlarmFtpTextmandatory Message text to store on the FTP server. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.27 |
wtWebioAn1GraphAlarmFtpClearTextmandatory Alarm clear message to store on the FTP server. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.28 |
wtWebioAn1GraphAlarmFtpOptionsmandatory Binary coded options, select only one option at the same time:STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… | OctetStringr/w Constraints: range: 4-4 | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.29 |
wtWebioAn1GraphAlarmTimerCronmandatory This entry contains 5 text fields space or tab seperated for time trigger definition.Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separately. 1: Minutes Rang… | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.30 |
.1.3.6.1.4.1.5040.1.2.8.3.2.1
·
1 row entry
·
7 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphPortTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-US-MIB::wtWebioAn1GraphPortTable'
List of settings depending on the sensor number.
Sensor parameters for the individual sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebioAn1GraphPortNamemandatory Name of the sensor. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.2.1.1.1 |
wtWebioAn1GraphPortTextmandatory Description of the sensor. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.2.1.1.2 |
wtWebioAn1GraphPortOffset1mandatory Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.2.1.1.3 |
wtWebioAn1GraphPortTemperature1mandatory Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.2.1.1.4 |
wtWebioAn1GraphPortOffset2mandatory Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.2.1.1.5 |
wtWebioAn1GraphPortTemperature2mandatory Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.2.1.1.6 |
wtWebioAn1GraphPortCommentmandatory Offset calibration: informations of date, name of operator, reference devices. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.2.1.1.7 |