WebGraph-Thermometer-US-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
7
Rows
7
Columns
42
.1.3.6.1.4.1.5040.1.2.8.1.2
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-US-MIB::wtWebioAn1GraphSensorTable'
List of sensors.
Temperature sensor numbers.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphSensorNomandatory
Temperature sensor number.
|
Integer32 Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.8.1.2.1.1 |
.1.3.6.1.4.1.5040.1.2.8.1.3
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphTempValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-US-MIB::wtWebioAn1GraphTempValueTable'
List of temperature values corresponding to the channel numbers.
Temperatures of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphTempValuemandatory
Temperature value of the sensor, ASCII, 5 characters in length.
|
OctetString Constraints: range: 5-5 |
.1.3.6.1.4.1.5040.1.2.8.1.3.1.1 |
.1.3.6.1.4.1.5040.1.2.8.1.4
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphBinaryTempValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-US-MIB::wtWebioAn1GraphBinaryTempValueTable'
List of binary temperature values corresponding to the channel numbers.
Binary temperature values of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphBinaryTempValuemandatory
Binary temperature value of the sensor in 1/10 degrees Celsius,
signed number, 0x7FFF indicates an invalid measured value. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.8.1.4.1.1 |
.1.3.6.1.4.1.5040.1.2.8.3.1.4.4
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphSensorColorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-US-MIB::wtWebioAn1GraphSensorColorTable'
List of sensor colors for the praphical presentation.
Index numbers of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphSensorColormandatory
Color of the sensors at the praphical presention.
|
OctetStringr/w Constraints: range: 3-3 |
.1.3.6.1.4.1.5040.1.2.8.3.1.4.4.1.1 |
.1.3.6.1.4.1.5040.1.2.8.3.1.5.2
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphAlarmIfTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-US-MIB::wtWebioAn1GraphAlarmIfTable'
List of alarm indices.
Numbers of the alarms.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphAlarmNomandatory
Alarm number.
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.5040.1.2.8.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.8.3.1.5.3
·
1 row entry
·
30 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-US-MIB::wtWebioAn1GraphAlarmTable'
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphAlarmTriggermandatory
Binary coded trigger conditions:
Octet 1: unused Octet 2: unused Octet 3: Bit 0: Timer Bit 1: ColdStart Bit 2: WarmStart Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2: Sensor 3 Bit 3: Sensor 4 B… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.1 |
|
wtWebioAn1GraphAlarmMinmandatory
Minimum temperature in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.2 |
|
wtWebioAn1GraphAlarmMaxmandatory
Maximum temperature in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.3 |
|
wtWebioAn1GraphAlarmHysteresismandatory
Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.4 |
|
wtWebioAn1GraphAlarmDelaymandatory
Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes). |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.5 |
|
wtWebioAn1GraphAlarmIntervalmandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.6 |
|
wtWebioAn1GraphAlarmEnablemandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.7 |
|
wtWebioAn1GraphAlarmEMailAddrmandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.8 |
|
wtWebioAn1GraphAlarmMailSubjectmandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.9 |
|
wtWebioAn1GraphAlarmMailTextmandatory
Alarm mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.10 |
|
wtWebioAn1GraphAlarmManagerIPmandatory
Name or IP address of the SNMP Manager which accepts the trap.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.11 |
|
wtWebioAn1GraphAlarmTrapTextmandatory
This text is sent in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.12 |
|
wtWebioAn1GraphAlarmMailOptionsmandatory
Binary coded options:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Thermo.csv Enable Bit 1-7: unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.13 |
|
wtWebioAn1GraphAlarmTcpIpAddrmandatory
Name or IP address of the TCP server which accepts the trap.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.14 |
|
wtWebioAn1GraphAlarmTcpPortmandatory
Port number of the TCP server which accepts the trap.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.15 |
|
wtWebioAn1GraphAlarmTcpTextmandatory
This text is sent in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.16 |
|
wtWebioAn1GraphAlarmClearMailSubjectmandatory
Subject line for alarm clear mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.17 |
|
wtWebioAn1GraphAlarmClearMailTextmandatory
Alarm clear mail text: <Tn> provides the current temperature; n = 1..8. <Z> provides the current time.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.18 |
|
wtWebioAn1GraphAlarmClearTrapTextmandatory
This text is sent in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.19 |
|
wtWebioAn1GraphAlarmClearTcpTextmandatory
This text is sent in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.20 |
|
wtWebioAn1GraphAlarmSyslogIpAddrmandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
RFC1155-SMIIpAddressr/w Type Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.21 |
|
wtWebioAn1GraphAlarmSyslogPortmandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.22 |
|
wtWebioAn1GraphAlarmSyslogTextmandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.23 |
|
wtWebioAn1GraphAlarmSyslogClearTextmandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.24 |
|
wtWebioAn1GraphAlarmFtpDataPortmandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.25 |
|
wtWebioAn1GraphAlarmFtpFileNamemandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.26 |
|
wtWebioAn1GraphAlarmFtpTextmandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.27 |
|
wtWebioAn1GraphAlarmFtpClearTextmandatory
Alarm clear message to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.28 |
|
wtWebioAn1GraphAlarmFtpOptionsmandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.29 |
|
wtWebioAn1GraphAlarmTimerCronmandatory
This entry contains 5 text fields space or tab seperated for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separately. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.1.5.3.1.30 |
.1.3.6.1.4.1.5040.1.2.8.3.2.1
·
1 row entry
·
7 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphPortTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-US-MIB::wtWebioAn1GraphPortTable'
List of settings depending on the sensor number.
Sensor parameters for the individual sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphPortNamemandatory
Name of the sensor.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.2.1.1.1 |
|
wtWebioAn1GraphPortTextmandatory
Description of the sensor.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.2.1.1.2 |
|
wtWebioAn1GraphPortOffset1mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.2.1.1.3 |
|
wtWebioAn1GraphPortTemperature1mandatory
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.2.1.1.4 |
|
wtWebioAn1GraphPortOffset2mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.2.1.1.5 |
|
wtWebioAn1GraphPortTemperature2mandatory
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.2.1.1.6 |
|
wtWebioAn1GraphPortCommentmandatory
Offset calibration: informations of date, name of operator, reference devices.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.8.3.2.1.1.7 |