.1.3.6.1.4.1.5040.1.2.38.1.2
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphNtcSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcSensorTable'
List of sensors.
Temperature sensor numbers.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebioAn1GraphNtcSensorNomandatory Temperature sensor number. | Integer32 Constraints: range: 1-1 | .1.3.6.1.4.1.5040.1.2.38.1.2.1.1 |
.1.3.6.1.4.1.5040.1.2.38.1.3
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphNtcTempValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcTempValueTable'
List of temperature values corresponding to the channel numbers.
Temperatures of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebioAn1GraphNtcTempValuemandatory Temperature value of the sensor, ASCII, 5 characters in length. | OctetString Constraints: range: 5-5 | .1.3.6.1.4.1.5040.1.2.38.1.3.1.1 |
.1.3.6.1.4.1.5040.1.2.38.1.4
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphNtcBinaryTempValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcBinaryTempValueTable'
List of binary temperature values corresponding to the channel numbers.
Binary temperature values of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebioAn1GraphNtcBinaryTempValuemandatory Binary temperature value of the sensor in 1/10 degrees Celsius,signed number, 0x7FFF indicates an invalid measured value. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.5040.1.2.38.1.4.1.1 |
.1.3.6.1.4.1.5040.1.2.38.1.8
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphNtcTempValuePktTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcTempValuePktTable'
List of temperature values corresponding to the channel numbers.
Temperatures of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebioAn1GraphNtcTempValuePktmandatory Temperature value of the sensor, ASCII, 5 characters in length, decimal point. | OctetString Constraints: range: 5-5 | .1.3.6.1.4.1.5040.1.2.38.1.8.1.1 |
.1.3.6.1.4.1.5040.1.2.38.3.1.4.4
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphNtcSensorColorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcSensorColorTable'
List of sensor colors for the praphical presentation.
Index numbers of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebioAn1GraphNtcSensorColormandatory Color of the sensors at the praphical presention. | OctetStringr/w Constraints: range: 3-3 | .1.3.6.1.4.1.5040.1.2.38.3.1.4.4.1.1 |
.1.3.6.1.4.1.5040.1.2.38.3.1.5.2
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphNtcAlarmIfTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcAlarmIfTable'
List of alarm indices.
Numbers of the alarms.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebioAn1GraphNtcAlarmNomandatory Alarm number. | Integer32 Constraints: range: 1-8 | .1.3.6.1.4.1.5040.1.2.38.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.38.3.1.5.3
·
1 row entry
·
44 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphNtcAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcAlarmTable'
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebioAn1GraphNtcAlarmTriggermandatory Binary coded trigger conditions:Octet 1: unused Octet 2: unused Octet 3: Bit 0: Timer Bit 1: ColdStart Bit 2: WarmStart Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2: Sensor 3 Bit 3: Sensor 4 B… | OctetStringr/w Constraints: range: 4-4 | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.1 |
wtWebioAn1GraphNtcAlarmMinmandatory Minimum temperature in degrees with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.2 |
wtWebioAn1GraphNtcAlarmMaxmandatory Maximum temperature in degrees with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.3 |
wtWebioAn1GraphNtcAlarmHysteresismandatory Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.), in degrees with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.4 |
wtWebioAn1GraphNtcAlarmDelaymandatory Alarm will be delayed by setting this time while stable alarm condition occur (time in minutes). | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.5 |
wtWebioAn1GraphNtcAlarmIntervalmandatory Send interval for alarm messages. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.6 |
wtWebioAn1GraphNtcAlarmEnablemandatory Binary coded alarm enable:Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable | OctetStringr/w Constraints: range: 4-4 | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.7 |
wtWebioAn1GraphNtcAlarmEMailAddrmandatory E-Mail address for sending the alarm mail to. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.8 |
wtWebioAn1GraphNtcAlarmMailSubjectmandatory Subject line for alarm mail. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.9 |
wtWebioAn1GraphNtcAlarmMailTextmandatory Alarm mail text: <Tn> provides the current temperature; n = 1..8.<Z> provides the current time. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.10 |
wtWebioAn1GraphNtcAlarmManagerIPmandatory Name or IP address of the SNMP Manager which accepts the trap. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.11 |
wtWebioAn1GraphNtcAlarmTrapTextmandatory This text is sent in the trap body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.12 |
wtWebioAn1GraphNtcAlarmMailOptionsmandatory Binary coded options:Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Thermo.csv Enable Bit 1 : CSV-Data_since_last_report Bit 2-7: unused | OctetStringr/w Constraints: range: 4-4 | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.13 |
wtWebioAn1GraphNtcAlarmTcpIpAddrmandatory Name or IP address of the TCP server which accepts the trap. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.14 |
wtWebioAn1GraphNtcAlarmTcpPortmandatory Port number of the TCP server which accepts the trap. | Integer32r/w Constraints: range: 1-65535 | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.15 |
wtWebioAn1GraphNtcAlarmTcpTextmandatory This text is sent in the TCP trap body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.16 |
| Subject line for alarm clear mail. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.17 |
wtWebioAn1GraphNtcAlarmClearMailTextmandatory Alarm clear mail text: <Tn> provides the current temperature; n = 1..8. <Z> provides the current time. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.18 |
wtWebioAn1GraphNtcAlarmClearTrapTextmandatory This text is sent in the trap body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.19 |
wtWebioAn1GraphNtcAlarmClearTcpTextmandatory This text is sent in the TCP trap body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.20 |
wtWebioAn1GraphNtcAlarmSyslogIpAddrmandatory IP address of the syslog server to which the Webio device should send syslog messages. | RFC1155-SMIIpAddressr/w Type Constraints: range: 4 | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.21 |
wtWebioAn1GraphNtcAlarmSyslogPortmandatory Port number of the syslog server to which the Webio device should send syslog messages. | Integer32r/w Constraints: range: 1-65535 | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.22 |
wtWebioAn1GraphNtcAlarmSyslogTextmandatory Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.This text appears in the following syslog message body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.23 |
| Every message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.24 |
wtWebioAn1GraphNtcAlarmFtpDataPortmandatory Local data port: 1..65535 or AUTO: the next free port will be assigned. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.25 |
wtWebioAn1GraphNtcAlarmFtpFileNamemandatory Name of the file including path informations. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.26 |
wtWebioAn1GraphNtcAlarmFtpTextmandatory Message text to store on the FTP server. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.27 |
wtWebioAn1GraphNtcAlarmFtpClearTextmandatory Alarm clear message to store on the FTP server. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.28 |
wtWebioAn1GraphNtcAlarmFtpOptionmandatory Binary coded options, select only one option at the same time:STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… | OctetStringr/w Constraints: range: 4-4 | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.29 |
wtWebioAn1GraphNtcAlarmTimerCronmandatory This entry contains 5 text fields space or tab seperated for time trigger definition.Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separately. 1: Minutes Rang… | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.30 |
wtWebioAn1GraphNtcAlarmDeltaTempmandatory Maximum rate of change degrees/min with maximum 2 decimal places.Compared with the average of a period of 5 minutes. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.31 |
wtWebioAn1GraphNtcAlarmNamemandatory Alert name | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.39 |
wtWebioAn1GraphNtcAlarmActivemandatory Alert active1 = ON 0 = OFF | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.40 |
| Binary coded options, select only one option at the same time: OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : HHTP Request Authentication enable | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.61 |
| HTTP Request: User | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.62 |
| HTTP Request: Password | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.63 |
wtWebioAn1GraphNtcAlarmHttpReqSetUrlmandatory HTTP Request: Set URL | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.64 |
| HTTP Request: Clear URL | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.65 |
| HTTP Request: Server Port | Integer32r/w Constraints: range: 1-65535 | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.66 |
wtWebioAn1GraphNtcAlarmMqttTopicPathmandatory MQTT Publish: Topic path | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.67 |
| MQTT Publish: Topic SET message | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.68 |
| MQTT Publish: Topic CLEAR message | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.69 |
| Binary coded options: OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : Sensor 0 | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.70 |
wtWebioAn1GraphNtcAlarmLimitWindowmandatory If window type is INSIDE the alarm is genereted when the temperatureis greater minumum value and lower than maximum value. If window type is OUTSIDE the alarm is generated when the measured value is lower than the mini… | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.71 |
.1.3.6.1.4.1.5040.1.2.38.3.1.6.2.3
·
1 row entry
·
2 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphNtc2SensorColorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtc2SensorColorTable'
List of sensor colors for the praphical presentation.
Numbers of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
| Color of the sensors at the praphical presention. | OctetStringr/w Constraints: range: 3-3 | .1.3.6.1.4.1.5040.1.2.38.3.1.6.2.3.1.1 |
| Assignes one of 4 scales to a sensor: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Use Scale 1 Bit 1-7: unused | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.1.6.2.3.1.2 |
.1.3.6.1.4.1.5040.1.2.38.3.2.1
·
1 row entry
·
7 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebioAn1GraphNtcPortTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcPortTable'
List of settings depending on the sensor number.
Sensor parameters for the individual sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebioAn1GraphNtcPortNamemandatory Name of the sensor. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.2.1.1.1 |
wtWebioAn1GraphNtcPortTextmandatory Description of the sensor. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.2.1.1.2 |
wtWebioAn1GraphNtcPortOffset1mandatory Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.2.1.1.3 |
wtWebioAn1GraphNtcPortTemperature1mandatory Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.2.1.1.4 |
wtWebioAn1GraphNtcPortOffset2mandatory Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.2.1.1.5 |
wtWebioAn1GraphNtcPortTemperature2mandatory Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.2.1.1.6 |
wtWebioAn1GraphNtcPortCommentmandatory Offset calibration: informations of date, name of operator, reference devices. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.38.3.2.1.1.7 |