WebGraph-Thermometer-NTC-US-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
9
Rows
9
Columns
59
.1.3.6.1.4.1.5040.1.2.38.1.2 · 1 row entry · 1 columns
Uses the webgraph variant from /opt/observium/mibs/webgraph.
Command help
Walk wtWebioAn1GraphNtcSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcSensorTable'
List of sensors.
wtWebioAn1GraphNtcSensorEntry row .1.3.6.1.4.1.5040.1.2.38.1.2.1
Temperature sensor numbers.
Column Syntax OID
Temperature sensor number.
Integer32
Constraints:
range: 1-1
.1.3.6.1.4.1.5040.1.2.38.1.2.1.1
.1.3.6.1.4.1.5040.1.2.38.1.3 · 1 row entry · 1 columns
Uses the webgraph variant from /opt/observium/mibs/webgraph.
Command help
Walk wtWebioAn1GraphNtcTempValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcTempValueTable'
List of temperature values corresponding to the channel numbers.
wtWebioAn1GraphNtcTempValueEntry row .1.3.6.1.4.1.5040.1.2.38.1.3.1
Temperatures of the sensors.
Column Syntax OID
Temperature value of the sensor, ASCII, 5 characters in length.
OctetString
Constraints:
range: 5-5
.1.3.6.1.4.1.5040.1.2.38.1.3.1.1
.1.3.6.1.4.1.5040.1.2.38.1.4 · 1 row entry · 1 columns
Uses the webgraph variant from /opt/observium/mibs/webgraph.
Command help
Walk wtWebioAn1GraphNtcBinaryTempValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcBinaryTempValueTable'
List of binary temperature values corresponding to the channel numbers.
wtWebioAn1GraphNtcBinaryTempValueEntry row .1.3.6.1.4.1.5040.1.2.38.1.4.1
Binary temperature values of the sensors.
Column Syntax OID
Binary temperature value of the sensor in 1/10 degrees Celsius,
signed number, 0x7FFF indicates an
invalid measured value.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5040.1.2.38.1.4.1.1
.1.3.6.1.4.1.5040.1.2.38.1.8 · 1 row entry · 1 columns
Uses the webgraph variant from /opt/observium/mibs/webgraph.
Command help
Walk wtWebioAn1GraphNtcTempValuePktTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcTempValuePktTable'
List of temperature values corresponding to the channel numbers.
wtWebioAn1GraphNtcTempValuePktEntry row .1.3.6.1.4.1.5040.1.2.38.1.8.1
Temperatures of the sensors.
Column Syntax OID
Temperature value of the sensor, ASCII, 5 characters in length, decimal point.
OctetString
Constraints:
range: 5-5
.1.3.6.1.4.1.5040.1.2.38.1.8.1.1
.1.3.6.1.4.1.5040.1.2.38.3.1.4.4 · 1 row entry · 1 columns
Uses the webgraph variant from /opt/observium/mibs/webgraph.
Command help
Walk wtWebioAn1GraphNtcSensorColorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcSensorColorTable'
List of sensor colors for the praphical presentation.
wtWebioAn1GraphNtcSensorColorEntry row .1.3.6.1.4.1.5040.1.2.38.3.1.4.4.1
Index numbers of the sensors.
Column Syntax OID
Color of the sensors at the praphical presention.
OctetStringr/w
Constraints:
range: 3-3
.1.3.6.1.4.1.5040.1.2.38.3.1.4.4.1.1
.1.3.6.1.4.1.5040.1.2.38.3.1.5.2 · 1 row entry · 1 columns
Uses the webgraph variant from /opt/observium/mibs/webgraph.
Command help
Walk wtWebioAn1GraphNtcAlarmIfTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcAlarmIfTable'
List of alarm indices.
wtWebioAn1GraphNtcAlarmIfEntry row .1.3.6.1.4.1.5040.1.2.38.3.1.5.2.1
Numbers of the alarms.
Column Syntax OID
Alarm number.
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.5040.1.2.38.3.1.5.2.1.1
.1.3.6.1.4.1.5040.1.2.38.3.1.5.3 · 1 row entry · 44 columns
Uses the webgraph variant from /opt/observium/mibs/webgraph.
Command help
Walk wtWebioAn1GraphNtcAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcAlarmTable'
List of settings depending on the alarm number.
wtWebioAn1GraphNtcAlarmEntry row .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1
Alarm parameters of the individual alarms.
Column Syntax OID
Binary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3:
Bit 0: Timer
Bit 1: ColdStart
Bit 2: WarmStart

Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2: Sensor 3
Bit 3: Sensor 4
B…
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.1
Minimum temperature in degrees with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.2
Maximum temperature in degrees with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.3
Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.4
Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes).
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.5
Send interval for alarm messages.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.6
Binary coded alarm enable:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Mail Enable
Bit 1: SNMP Trap enable
Bit 2: TCP Client enable
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.7
E-Mail address for sending the alarm mail to.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.8
Subject line for alarm mail.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.9
Alarm mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.10
Name or IP address of the SNMP Manager which accepts the trap.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.11
This text is sent in the trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.12
Binary coded options:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Attach Thermo.csv Enable
Bit 1 : CSV-Data_since_last_report
Bit 2-7: unused
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.13
Name or IP address of the TCP server which accepts the trap.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.14
Port number of the TCP server which accepts the trap.
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.15
This text is sent in the TCP trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.16
Subject line for alarm clear mail.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.17
Alarm clear mail text: <Tn> provides the current temperature; n = 1..8. <Z> provides the current time.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.18
This text is sent in the trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.19
This text is sent in the TCP trap body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.20
IP address of the syslog server to which the Webio device should send syslog messages.
RFC1155-SMIIpAddressr/w
Type Constraints:
range: 4
.1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.21
Port number of the syslog server to which the Webio device should send syslog messages.
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.22
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.23
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.24
Local data port: 1..65535 or AUTO: the next free port will be assigned.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.25
Name of the file including path informations.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.26
Message text to store on the FTP server.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.27
Alarm clear message to store on the FTP server.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.28
Binary coded options, select only one option at the same time:
STORE = replace file
APPEND = append message at the end of the file

Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : STOR…
OctetStringr/w
Constraints:
range: 4-4
.1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.29
This entry contains 5 text fields space or tab seperated for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month
are interpreted separately.
1: Minutes Rang…
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.30
Maximum rate of change degrees/min with maximum 2 decimal places.
Compared with the average of a period of 5 minutes.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.31
Alert name
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.39
Alert active
1 = ON
0 = OFF
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.40
Binary coded options, select only one option at the same time:
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4, Bit 1-7: unused
Bit 0 : HHTP Request Authentication enable
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.61
HTTP Request: User
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.62
HTTP Request: Password
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.63
HTTP Request: Set URL
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.64
HTTP Request: Clear URL
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.65
HTTP Request: Server Port
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.66
MQTT Publish: Topic path
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.67
MQTT Publish: Topic SET message
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.68
MQTT Publish: Topic CLEAR message
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.69
Binary coded options:
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4, Bit 1-7: unused
Bit 0 : Sensor 0
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.70
If window type is INSIDE the alarm is genereted when the temperature
is greater minumum value and lower than maximum value. If window type is OUTSIDE
the alarm is generated when the measured value is lower than the mini…
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.5.3.1.71
.1.3.6.1.4.1.5040.1.2.38.3.1.6.2.3 · 1 row entry · 2 columns
Uses the webgraph variant from /opt/observium/mibs/webgraph.
Command help
Walk wtWebioAn1GraphNtc2SensorColorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtc2SensorColorTable'
List of sensor colors for the praphical presentation.
wtWebioAn1GraphNtc2SensorColorEntry row .1.3.6.1.4.1.5040.1.2.38.3.1.6.2.3.1
Numbers of the sensors.
Column Syntax OID
Color of the sensors at the praphical presention.
OctetStringr/w
Constraints:
range: 3-3
.1.3.6.1.4.1.5040.1.2.38.3.1.6.2.3.1.1
Assignes one of 4 scales to a sensor:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Use Scale 1
Bit 1-7: unused
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.1.6.2.3.1.2

wtWebioAn1GraphNtcPortTable

table mandatory
.1.3.6.1.4.1.5040.1.2.38.3.2.1 · 1 row entry · 7 columns
Uses the webgraph variant from /opt/observium/mibs/webgraph.
Command help
Walk wtWebioAn1GraphNtcPortTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-Thermometer-NTC-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-Thermometer-NTC-US-MIB::wtWebioAn1GraphNtcPortTable'
List of settings depending on the sensor number.
wtWebioAn1GraphNtcPortEntry row .1.3.6.1.4.1.5040.1.2.38.3.2.1.1
Sensor parameters for the individual sensors.
Column Syntax OID
Name of the sensor.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.2.1.1.1
Description of the sensor.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.2.1.1.2
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.2.1.1.3
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.2.1.1.4
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.2.1.1.5
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
OctetStringr/w .1.3.6.1.4.1.5040.1.2.38.3.2.1.1.6
Offset calibration: informations of date, name of operator, reference devices.