.1.3.6.1.4.1.5040.1.2.35.1.2
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphAirQualitySensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-OLD-Air-Quality-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-OLD-Air-Quality-US-MIB::wtWebGraphAirQualitySensorTable'
List of sensors.
List of sensor numbers.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebGraphAirQualitySensorNomandatory Sensor number. | Integer32 Constraints: range: 1-2 | .1.3.6.1.4.1.5040.1.2.35.1.2.1.1 |
.1.3.6.1.4.1.5040.1.2.35.1.3
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphAirQualityTempValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-OLD-Air-Quality-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-OLD-Air-Quality-US-MIB::wtWebGraphAirQualityTempValueTable'
List of measurement values corresponding to the channel numbers.
Measurement values of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebGraphAirQualityTempValuemandatory Measurement value of the sensor, ASCII, 5 characters in length. | OctetString Constraints: range: 5-5 | .1.3.6.1.4.1.5040.1.2.35.1.3.1.1 |
.1.3.6.1.4.1.5040.1.2.35.1.4
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphAirQualityBinaryTempValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-OLD-Air-Quality-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-OLD-Air-Quality-US-MIB::wtWebGraphAirQualityBinaryTempValueTable'
List of binary measurement values corresponding to the channel numbers.
Binary measurement values of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebGraphAirQualityBinaryTempValuemandatory Binary measurement value of the sensor in 1/10 degrees Celsius, 1/10 per centor 1/10 ppm, signed number, 0x7FFFFFFF indicates an invalid measured value. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.5040.1.2.35.1.4.1.1 |
.1.3.6.1.4.1.5040.1.2.35.1.8
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphAirQualityTempValuePktTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-OLD-Air-Quality-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-OLD-Air-Quality-US-MIB::wtWebGraphAirQualityTempValuePktTable'
List of measurement values corresponding to the channel numbers.
Measurement values of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebGraphAirQualityTempValuePktmandatory Measurement value of the sensor, ASCII, 5 characters in length, delimeter is decimal point. | OctetString Constraints: range: 5-5 | .1.3.6.1.4.1.5040.1.2.35.1.8.1.1 |
.1.3.6.1.4.1.5040.1.2.35.3.1.5.2
·
1 row entry
·
1 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphAirQualityAlarmIfTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-OLD-Air-Quality-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-OLD-Air-Quality-US-MIB::wtWebGraphAirQualityAlarmIfTable'
List of alarm indices.
Numbers of the alarms.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebGraphAirQualityAlarmNomandatory Alarm number. | Integer32 Constraints: range: 1-8 | .1.3.6.1.4.1.5040.1.2.35.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.35.3.1.5.3
·
1 row entry
·
40 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphAirQualityAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-OLD-Air-Quality-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-OLD-Air-Quality-US-MIB::wtWebGraphAirQualityAlarmTable'
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebGraphAirQualityAlarmTriggermandatory Binary coded trigger conditions:Octet 1: unused Octet 2: unused Octet 3: Bit 0: Timer Bit 1: ColdStart Bit 2: WarmStart Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused | OctetStringr/w Constraints: range: 4-4 | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.1 |
wtWebGraphAirQualityAlarmMinmandatory Minimum temperature in degrees with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.2 |
wtWebGraphAirQualityAlarmMaxmandatory Maximum temperature in degrees with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.3 |
wtWebGraphAirQualityAlarmHysteresismandatory Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.), in degrees with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.4 |
wtWebGraphAirQualityAlarmDelaymandatory Alarm will be delayed by setting this time while stable alarm condition occur (time in minutes). | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.5 |
wtWebGraphAirQualityAlarmIntervalmandatory Send interval for alarm messages. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.6 |
wtWebGraphAirQualityAlarmEnablemandatory Binary coded alarm enable:Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable | OctetStringr/w Constraints: range: 4-4 | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.7 |
wtWebGraphAirQualityAlarmEMailAddrmandatory E-Mail address for sending the alarm mail to. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.8 |
wtWebGraphAirQualityAlarmMailSubjectmandatory Subject line for alarm mail. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.9 |
wtWebGraphAirQualityAlarmMailTextmandatory Alarm mail text: <Tn> provides the current temperature; n = 1..8.<Z> provides the current time. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.10 |
wtWebGraphAirQualityAlarmManagerIPmandatory Name or IP address of the SNMP Manager which accepts the trap. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.11 |
wtWebGraphAirQualityAlarmTrapTextmandatory This text is sent in the trap body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.12 |
wtWebGraphAirQualityAlarmMailOptionsmandatory Binary coded options:Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Thermo.csv Enable Bit 1 : CSV-Data_since_last_report Bit 2-7: unused | OctetStringr/w Constraints: range: 4-4 | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.13 |
wtWebGraphAirQualityAlarmTcpIpAddrmandatory Name or IP address of the TCP server which accepts the trap. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.14 |
wtWebGraphAirQualityAlarmTcpPortmandatory Port number of the TCP server which accepts the trap. | Integer32r/w Constraints: range: 1-65535 | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.15 |
wtWebGraphAirQualityAlarmTcpTextmandatory This text is sent in the TCP trap body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.16 |
| Subject line for alarm clear mail. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.17 |
| Alarm clear mail text: <Tn> provides the current temperature; n = 1..8. <Z> provides the current time. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.18 |
| This text is sent in the trap body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.19 |
| This text is sent in the TCP trap body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.20 |
wtWebGraphAirQualityAlarmDeltaTempmandatory Maximum rate of change degrees/min with maximum 2 decimal places.Compared with the average of a period of 5 minutes. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.21 |
wtWebGraphAirQualityAlarmRHMinmandatory Minimum rel. Humidity in percent with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.22 |
wtWebGraphAirQualityAlarmRHMaxmandatory Maximum rel.Humidity in percent with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.23 |
| Hysteresis of rel. Humidity in percent with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.24 |
wtWebGraphAirQualityAlarmAHMinmandatory Minimum abs. Humidity in g/(m*m*m) with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.25 |
wtWebGraphAirQualityAlarmAHMaxmandatory Maximum abs. Humidity in g/(m*m*m) with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.26 |
| IP address of the syslog server to which the Webio device should send syslog messages. | RFC1155-SMIIpAddressr/w Type Constraints: range: 4 | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.27 |
wtWebGraphAirQualityAlarmSyslogPortmandatory Port number of the syslog server to which the Webio device should send syslog messages. | Integer32r/w Constraints: range: 1-65535 | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.28 |
wtWebGraphAirQualityAlarmSyslogTextmandatory Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.This text appears in the following syslog message body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.29 |
| Every message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.30 |
wtWebGraphAirQualityAlarmFtpDataPortmandatory Local data port: 1..65535 or AUTO: the next free port will be assigned. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.31 |
wtWebGraphAirQualityAlarmFtpFileNamemandatory Name of the file including path informations. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.32 |
wtWebGraphAirQualityAlarmFtpTextmandatory Message text to store on the FTP server. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.33 |
| Alarm clear message to store on the FTP server. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.34 |
wtWebGraphAirQualityAlarmFtpOptionmandatory Binary coded options, select only one option at the same time:STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… | OctetStringr/w Constraints: range: 4-4 | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.35 |
wtWebGraphAirQualityAlarmTimerCronmandatory This entry contains 5 space or tab seperated text fields for time trigger definition.Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.36 |
wtWebGraphAirQualityAlarmVocMaxmandatory Maximum VOC in ppm with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.37 |
| Hysteresis of VOC in ppm with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.38 |
wtWebGraphAirQualityAlarmNamemandatory Alert name | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.39 |
wtWebGraphAirQualityAlarmActivemandatory Alert active1 = ON 0 = OFF | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.40 |
.1.3.6.1.4.1.5040.1.2.35.3.1.6.2.3
·
1 row entry
·
2 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphAirQualitySensorColorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-OLD-Air-Quality-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-OLD-Air-Quality-US-MIB::wtWebGraphAirQualitySensorColorTable'
List of sensor colors for the praphical presentation.
Numbers of the sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
| Color of the sensors at the praphical presention. | OctetStringr/w Constraints: range: 3-3 | .1.3.6.1.4.1.5040.1.2.35.3.1.6.2.3.1.1 |
| Assignes one of 4 scales to a sensor: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Use Scale 1 Bit 1 : Use Scale 2 Bit 2 : Use Scale 3 Bit 3-7: unused | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.1.6.2.3.1.2 |
.1.3.6.1.4.1.5040.1.2.35.3.2.1
·
1 row entry
·
7 columns
Uses the webgraph variant from
Command help
/opt/observium/mibs/webgraph.
Walk wtWebGraphAirQualityPortTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'WebGraph-OLD-Air-Quality-US-MIB' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'WebGraph-OLD-Air-Quality-US-MIB::wtWebGraphAirQualityPortTable'
List of settings depending on the sensor number.
Sensor parameters for the individual sensors.
Indexes
| Column | Syntax | OID |
|---|---|---|
wtWebGraphAirQualityPortNamemandatory Name of the sensor. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.2.1.1.1 |
wtWebGraphAirQualityPortTextmandatory Description of the sensor. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.2.1.1.2 |
wtWebGraphAirQualityPortOffset1mandatory Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.2.1.1.3 |
wtWebGraphAirQualityPortTemperature1mandatory Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.2.1.1.4 |
wtWebGraphAirQualityPortOffset2mandatory Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.2.1.1.5 |
wtWebGraphAirQualityPortTemperature2mandatory Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.2.1.1.6 |
wtWebGraphAirQualityPortCommentmandatory Offset calibration: informations of date, name of operator, reference devices. | OctetStringr/w | .1.3.6.1.4.1.5040.1.2.35.3.2.1.1.7 |